![Funk-Electronic Piciorgros RTU-81 User Manual Download Page 109](http://html1.mh-extra.com/html/funk-electronic-piciorgros/rtu-81/rtu-81_user-manual_2346370109.webp)
Funk-Electronic Piciorgros GmbH
RTU-810
V2.30 - Page 109 of 126
300-399
All Output Data in packed format and in this order:
Digital Output
Analog Output as 12 Bit values
32 virtual PicoLogo output registers
400-449
Digital Inputs, I/O port A0 is the LSB
450-599
Analog Inputs (if present) as 12 Bit values
The upper four Bit are set to 0000 (can be changed in future)
Virtual analog inputs are added after the physical inputs.
600-649
Counter, 16 Bit each.
The first counter relates to I/O port A0, followed by A1, … , B15
As factory default, the port A counters are set as event counter, the
port B counters are set to Time-Counters (resolution is one second)
650-689
Virtual analog inputs
These can be written by a locally connected equipment and will be
shown to the SCADA as normal analog input.
Refer to "3.5.1.3 Virtual analog I/O"
700-739
Virtual analog inputs
These can be written by a SCADA master as analog outputs and will
be shown to locally connected equipment.
Refer to "3.5.1.3 Virtual analog I/O"
750-799
Digital outputs, I/O-port C0 is the LSB
800-899
Analog Outputs (if present), first value reflects input D0.
Virtual analog outputs are added after the physical outputs.
6.1.2
Special Registers
This is a summary of special MODBUS registers which can be useful to gather status
information from the RTU-810.
Red values
are alternative register addresses for the same register which are mapped for
the best compatibility with the RTU/TRM-710 series.
Register
Function
Comment
1000
906
Device ID
0x0800 for RTU-810, 0x0810 for RTU-81
Will be set to RTU-710/TRM-710 device ID in the RTU-810 if the
RTU-710 compatibility mode is selected
1001
907
Main software
version
Firmware version of the RTU-810
1004
Hardware
revision
1008
908
Serial number
The serial number of the device
1010
1
Status/RSSI
Same as MODBUS register 1 described before
1030
953
Time YYMM
Current time: Year (High.Byte) and Month (Low Byte)
1031
954
Time DDhh
Current time: Day (High.Byte) and Hour (Low Byte)
1032
955
Time mmss
Current time: Minute (High.Byte) and Second (Low Byte)
1033
Time Weekday
Day of the week, 1(Monday) – 7 (Sunday)