VMP-IOMM-2018-2
Fulton Ltd
Page 84
APPENDIX - A
VMP Series
Dimensions & Specification
Technical Information
Sheet No. 128 Issue 3
Dimensions
Page 1 of 2
A
E
T
S
L
K
N
M
R
G
W
D
U
V
B
C
P
J
H
* Recommended height for service & maintenance
Note:
Dimensions mm
Note:
Dimensions are approximate and only intended as a guide to aid installation.
Note:
Minimum clearances of 600 mm to the side and back, and 900 mm in front of the unit are recommended for service and maintenance.
The boiler may be fitted with a 90
°
elbow spool piece, making the steam outlet connection higher.
MODEL: VMP
60
80
100
A Minimum Clearance*
3175
3302
3353
B Overall Width
1575
1727
1880
C Overall Depth
2540
2896
3022
D Overall Height
2984
3150
3200
E Boiler Height
2464
2540
2540
F Boiler Diameter
1397
1600
1753
G Gas Train Length
800
800
800
H Gas Inlet Height
2710
2790
2790
J Oil Inlet Height
2134
2260
2260
K Safety Valve Discharge Height
2670
2740
2740
L Steam Outlet Height
2134
2260
2260
M Feedwater Inlet Height
889
889
889
N Flue Outlet Height
2237
2413
2413
P Flue Diameter
305
356
356
R Main Boiler Blowdown Height
457
457
457
S Control Column Blowdown Height
1680
1750
1750
T Water Level Gauge (Sight Glass)
Blowdown Height
1680
1750
1750
U Sight Glass Stand Off
300
300
300
V Control Column Stand Off
300
300
300
W Fan Stand Off
750
750
750