The probe is supplied in two parts, the head and the tip. The tip should be screwed onto the head aligning the slot
in the top of the tip with the hole in the screwed shaft of the head.
Locate the pin provided into the slot/hole and secure with the lock nut.
Using the measurement from the old probe, cut the new probe to length and de-burr. Ensure both measurements
are taken from the underside of the hex. nut on the probe head.
Figure. 3 - High Integrity Water Level Probe
Ensure measurements are
taken from the underside of
the hex. nut on the probe
head.
Align the hole in the probe
head with the bottom of the
slot in the probe tip.
Hold the probe head secure
whilst fitting the probe tip.
Locknut
Locate the pin in the hole/slot
and secure with the locknut.