MAINTENANCE - 4
4.6
CLEANING WATER LEvEL PROBES
Low water
(red cable)
Solenoid valve
open
(yellow cable)
Solenoid
valve closed
(black cable)
Figure. 17 - Feedwater Tank Water Level Probes
Figure. 18 - Boiler Water Level Probes
Low water
(red cable)
Low water
(brown cable)
Pump on
(yellow cable)
Pump off
(black cable)
Feedwater Tank
Isolate the boiler electrics at the isolator on the front access panel and remove the boiler top
access panel.
Remove and clean the feedwater tank level probes taking note of probe lead positions.
For more information on the water level probes see
Appendix A - TI-103-Water Level Probes.
Boiler
Isolate the boiler electrics at the isolator on the front access panel and remove the boiler right
side access panel.
Remove and clean the boiler level probes taking note of probe lead positions.