Heat exchanger liquid temperature
thermistor
Heat exchanger outlet temperature thermistor short or open detected
1. Connector connection defective, open
2. Thermistor failure
3. Main PCB failure
OK
OK
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 8".
02-24
Heat Ex. Outlet Temp.
Thermistor Error
Trouble shooting 23
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
Indicate or Display:
Error code : 73
Outdoor unit : No indication
DC
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB CN71:1-2 voltage value =5V
Remove the thermistor from Main PCB, check the voltage.
If the voltage does not appear, replace Main PCB
, and execute
the check operation again.
THERMISTOR (PIPE.)
THERMISTOR (DIS.PIPE.)
CN71
BLACK
BLACK
BLACK
BLACK
4 3
2 1
4 3
2 1