01-08
Compressor
ON
OFF
Indoor fan
Setting air flow
OFF
10
30
60
180
60
180
60 10
30
(sec)
S-Lo
480rpm
( Fig 8 : Indoor Fan Control)
7. FAN CONTROL FOR ENERGY SAVING
When the air flow setting except AUTO mode, the indoor fan motor will run as shown in Fig.8.
( Factory setting)
Setting Description
Function Number
Setting Value
Disable
Enable
Remote controller
49
02
00
01
00 : When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01 : When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very
low speed.
02 : Enable or disable this function by remote controller setting.
Set to “00”or “01”when connecting a remote controller that cannot set
the Fan control for energy saving function or connecting a network converter.
To confirm if the remote controller has this setting,
refer to the operating manual of each remote controller.
AMP Air Conditioning