1-4. AUTO CHANGEOVER OPERATION
01-04
When the air conditioner is set to the Auto mode by remote controller, operation starts in the optimum
mode from among the Heating, Cooling, and Monitoring mode. During operation, the
optimum mode is automatically switched in accordance with temperature changes. The temperature
can be set between 18°C and 30°C in 0.5°C (wireless and 2WIRE remote controller)
Or 1.0°C (3WIRE remote controller) steps.
When operation starts, indoor fan and outdoor fan are operated for around 1 minutes.
Room temperature and outdoor temperature are sensed, and the operation mode is selected
in accordance with the table below.
<Monitoring mode>
( Table 4 : Operation mode selection table )
Room temperature (TR)
TR> Ts+2°C
Ts+2°C TR Ts -2°C
*
Middle zone
TR < Ts -2°C
Heating
When the compressor was stopped for 6 consecutive minutes by the temperature control function
after the Cooling or Heating mode was selected at above, operation is switched
to Monitoring and the operation mode is selected again.
When the middle zone is selected on the predetermining of the operation mode, the operation mode
before the changing to the monitor mode is selected.
1
2
3
1
( Fig.4 : Outdoor temperature zone selection )
Cooling
Operation mode
Temperature
25
°C
and over
25
°C
under
Heating
Cooling
Mode
*
If it's Middle zone, operation mode of indoor unit is selected as below.
(1). Same operation mode is selected as outdoor unit.
If outdoor unit is operating in Cooling and Heating mode,
indoor unit will be operated by the same operation mode.
(2). Selected by the outdoor temperature.
If outdoor unit is operating in other than Cooling and Heating mode, indoor unit will be operated
according to the outdoor temperature as below.
TR : Room temperature
Ts : Setting temperature