1-20. VARIOUS PROTECTIONS
1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENTION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas
temperature.
104°C
101°C
110°C
When the discharge temperature becomes higher than Temperature ,the compressor frequency
is decreased 20rps, and it continues to decrease the frequency for 20rps every 120 seconds until
the temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature , the control of
the compressor frequency is released.
When the discharge temperature becomes higher than Temperature ,the compressor is stopped
and the indoor unit LED starts blinking.
(Table14 : Discharge Temperature Over Rise Prevention Control / Release Temperature)
Temperature
Temperature
Temperature
01-21
The compressor frequency is controlled so that the outdoor unit input current does not exceeds
the current limit value that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
2. CURRENT RELEASE CONTROL
( Table 15 : Current release operation value / release value )
OT : Outdoor Temperature
OT : Outdoor Temperature
[ Heating ]
OT (Control / Release)
7.0A / 6.5A
9.0A / 8.5A
10.5A / 10.0A
17°C
12°C
[ Cooling ]
OT (Control / Release)
4.5A / 4.0A
4.5A / 4.0A
6.0A / 5.5A
50°C
12.0A / 11.5A
5 °C
8.5A / 8.0A
40°C
46°C
OT : Outdoor Temperature
OT : Outdoor Temperature
[ Heating ]
OT (Control / Release)
10.5A / 10.0A
13.0A / 12.5A
15.0A / 14.5A
17°C
12°C
[ Cooling ]
OT (Control / Release)
7.0A / 6.5A
7.0A / 6.5A
9.5A / 9.0A
50°C
17.0A / 16.5A
5 °C
12.0A / 11.5A
40°C
46°C
Model 18
Model 24