1-1. COOLING OPERATION
1-1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is 6.0°C higher than a set temperature,
the compressor operation frequency will attain to maximum performance.
* If the room temperature is 1.0°C lower than a set temperature, the compressor
will be stopped.
* When the room temperature is b6.0°C to -1.0°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Fig.1 based on the
fan speed mode and the outdoor temperature.
minimum
frequency
maximum
frequency
10rps
120rps
Hi
Me
Lo
Qu
102rps
102rps
60rps
51rps
43rps
37rps
55rps
55rps
49rps
49rps
49rps
43rps
25rps
34rps
34rps
34rps
A zone
B zone
C zone
D-F zone
Model 18
( Table 1 : Compressor Frequency Range )
( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )
01-01
111rps
111rps
80rps
62rps
47rps
40rps
67rps
67rps
56rps
56rps
56rps
47rps
25rps
34rps
34rps
34rps
A zone
B zone
C zone
D-F zone
Model 24
Fan speed mode
Outdoor air
temperature
A zone
B zone
C zone
D zone
E zone
F zone
When the room
temperature rises
When the room
temperature drops
36°C
32°C
21°C
12°C
2°C
34°C
30°C
19°C
10°C
0°C
AMP Air Conditioning
www.ampair.co.uk | [email protected]