Table
3.3
Distribution
Panel
Breaker
Characteristics
Power
Input
Unit/Device
Name
Breaker
Capacity
in
Customer's
Distribution
Panel
for
Use
in
Countries
Not
in
Europe
Breaker
Capacity
in
Customer's
Distribution
Panel
for
Use
in
Europe
200
to
240
VAC
Main
device
20
A
16
A
Power
distribution
box
30
A
32
A
3.3.3
Seawater
(Salt
Spray
Damage)
Due
to
the
salty
air,
a
large
volume
of
sea
salt
particles
are
suspended
in
the
air
near
coastal
areas.
If
these
sea
salt
particles
enter
computers,
they
may
cause
insulation
to
fail
and
parts
to
corrode
or
degrade
due
to
moisture
and
chemical
condensation.
Therefore,
computers
must
be
installed
far
from
coastal
areas.
The
installation
criteria
for
preventing
salt
spray
damage
from
sea
salt
particles
is
as
follows.
Criteria:
The
installation
is
not
at
sea
nor
within
0.5
km
from
the
seashore.
(An
exception
is
an
installation
using
air
conditioners
that
do
not
take
in
outside
air.)
3.4
Distribution
Panel
Cut-Off
Characteristics
The
characteristics
of
breakers
in
the
customer’s
distribution
panel
must
be
considered
so
that
the
FX700
main
unit
can
run
optimally.
Use
suitable
breakers
according
to
Use
a
long-time-delay
type
breaker
whose
cut-off
characteristics
correspond
to
phase
D
shown
in
(IEC898
or
DIN0641
Part
II).
Alternatively,
use
a
slower
breaker.
Chapter
3
Starting
Up
C120-0089-03EN
3.4
Distribution
Panel
Cut-Off
Characteristics
25