- 29 -
W
A
LL
MOU
N
TED
ASYG30, 36LMTA
10-3. Combination of external input and output
By combining the function setting of the indoor unit and rotary switch setting of the External input
and output PCB, you can select various combinations of functions.
Combination examples of external input and output are as follows:
NOTE:
Input of Operation/Stop depends on the setting of function setting 46.
00: Operation/Stop mode 1 (R.C. enabled)
01: (Setting prohibited)
02: Forced stop
03: Operation/Stop mode 2 (R.C. disabled)
Mode
Function
setting
External
input and
output PCB
(Rotary SW)
External input
Indoor unit
Input
External input and output PCB
CN2
CN313
CN314
Signal type
0-1
60-00
1
Operation/Stop
Operation/Stop
Not available
Edge
Operation
Stop
Pulse
0-2
60-00
2
Operation/Stop
Forced
Thermostat OFF
Not available
Edge
1—8
60-01 to
60-08
3 - 9, A
(Setting prohibited)
9
60-09
B
Operation/Stop
Forced
Thermostat OFF
Not available
Edge
10
60-10
C
Operation/Stop
Forced
Thermostat OFF
Not available
Edge
11
60-11
D
Operation/Stop
Forced
Thermostat OFF
Not available
Edge
12
60-12
D
Operation/Stop
Forced
Thermostat OFF
Not available
Edge
Mode
Function
setting
External
input and
output PCB
(Rotary SW)
External output
Indoor unit
Output
External input and output PCB
CN3
CN310
CN311
CN312
0-1
60-00
1
Operation/Stop
Operation/Stop
Error status
Indoor unit fan
operation status
0-2
60-00
2
Operation/Stop
Error status
Indoor unit fan
operation status
Not available
1—8
60-01 to
60-08
3 - 9, A
(Setting prohibited)
9
60-09
B
Error status
Operation/Stop
Indoor unit fan
operation status
Not available
10
60-10
C
Indoor unit fan
operation status
Operation/Stop
Error status
Not available
11
60-11
D
Not available
Operation/Stop
Indoor unit fan
operation status
Error status
12
60-12
D
Set point
attainment
status
Operation/Stop
Indoor unit fan
operation status
Error status
Summary of Contents for AOYG30LMTA
Page 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG30LMTA ASYG36LMTA ...
Page 20: ... 16 WALL MOUNTED ASYG30 36LMTA 5 Wiring diagram ...
Page 27: ... 23 WALL MOUNTED ASYG30 36LMTA 8 2 Sound level check point 0 8 m 1 m Microphone Microphone ...
Page 52: ... 48 WALL MOUNTED ASYG30 36LMTA ...
Page 53: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG30LMTA AOYG36LMTA ...
Page 59: ... 55 OUTDOOR UNIT AOYG30 36LMTA 3 Refrigerant circuit ...
Page 60: ... 56 OUTDOOR UNIT AOYG30 36LMTA 4 Wiring diagram ...