Set point attainment status
NOTE:
This function is valid only when function setting 96 is set to “01” (Primary unit) or “02”
(Secondary unit).
When the room temperature does not reach the set point at a room due to the lower cooling perfor-
mance caused by external factor such as the outdoor temperature change, signal is output to tell
the attainment status of set point.
When performing the server room control, both of the primary unit and secondary unit output the set
point attainment status if any of the unit is outputting alternative operation command.
Function
setting /
Rotary SW on External
input and output PCB
External output
Output
signal
Command
60-12 / D
Output of indoor unit
CN3
On
→
Off
Normal
Off
→
On
Set point
attainment
Output signal
Condition
Off
Reached the set point. (Tr
≤
Ts
α
+0.5)
On
Unreached the set point. (Tr > Ts
α
+2.5)
However, even if the set point unreached, the signal will not be output for 7 minutes
after power is turned on.
Tr > Tsα +2.5
Output: On
Output: Off
Tr ≤ Tsα +0.5
When starting operation*
*: When starting operation or resetting, judges the zone to descending direction.
Summary of Contents for AOYG30LMTA
Page 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG30LMTA ASYG36LMTA ...
Page 20: ... 16 WALL MOUNTED ASYG30 36LMTA 5 Wiring diagram ...
Page 27: ... 23 WALL MOUNTED ASYG30 36LMTA 8 2 Sound level check point 0 8 m 1 m Microphone Microphone ...
Page 52: ... 48 WALL MOUNTED ASYG30 36LMTA ...
Page 53: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG30LMTA AOYG36LMTA ...
Page 59: ... 55 OUTDOOR UNIT AOYG30 36LMTA 3 Refrigerant circuit ...
Page 60: ... 56 OUTDOOR UNIT AOYG30 36LMTA 4 Wiring diagram ...