- 57 -
O
U
T
D
OOR UNIT
AOY
G
30, 36
LMTA
5. Capacity compensation rate for pipe length and height
difference
5-1. Models: AOYG30LMTA and AOYG36LMTA
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5
7.5
10
20
30
40
50
Height difference H
(m)
Indoor unit is higher than
outdoor unit *1
30
-
-
-
-
0.932
0.929
0.924
20
-
-
-
0.945
0.947
0.945
0.940
10
-
-
0.984
0.961
0.963
0.960
0.956
7.5
-
0.988
0.988
0.965
0.967
0.964
0.959
5
0.992
0.992
0.992
0.968
0.971
0.968
0.963
0
1.000
1.000
1.000
0.976
0.979
0.976
0.971
Indoor unit is lower than
outdoor unit *2
-5
1.000
1.000
1.000
0.976
0.979
0.976
0.971
-7.5
-
1.000
1.000
0.976
0.979
0.976
0.971
-10
-
-
1.000
0.976
0.979
0.976
0.971
-20
-
-
-
0.976
0.979
0.976
0.971
-30
-
-
-
-
0.979
0.976
0.971
HEATING
Pipe length (m)
5
7.5
10
20
30
40
50
He
igh
t differ
ence
H (m)
Indoor unit is higher than
outdoor unit *1
30
-
-
-
-
0.816
0.756
0.686
20
-
-
-
0.872
0.816
0.756
0.686
10
-
-
0.991
0.872
0.816
0.756
0.686
7.5
-
1.000
0.991
0.872
0.816
0.756
0.686
5
1.000
1.000
0.991
0.872
0.816
0.756
0.686
0
1.000
1.000
0.991
0.872
0.816
0.756
0.686
Indoor unit is lower than
outdoor unit *2
-5
0.995
0.995
0.986
0.868
0.812
0.752
0.683
-7.5
-
0.993
0.983
0.866
0.810
0.750
0.681
-10
-
-
0.981
0.864
0.808
0.748
0.679
-20
-
-
-
0.855
0.799
0.740
0.672
-30
-
-
-
-
0.791
0.733
0.665
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit
*
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H
H
Summary of Contents for AOYG30LMTA
Page 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG30LMTA ASYG36LMTA ...
Page 20: ... 16 WALL MOUNTED ASYG30 36LMTA 5 Wiring diagram ...
Page 27: ... 23 WALL MOUNTED ASYG30 36LMTA 8 2 Sound level check point 0 8 m 1 m Microphone Microphone ...
Page 52: ... 48 WALL MOUNTED ASYG30 36LMTA ...
Page 53: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG30LMTA AOYG36LMTA ...
Page 59: ... 55 OUTDOOR UNIT AOYG30 36LMTA 3 Refrigerant circuit ...
Page 60: ... 56 OUTDOOR UNIT AOYG30 36LMTA 4 Wiring diagram ...