10. Safety devices
Type of
protection
Protection form
Model
AOYG30LMTA
AOYG36LMTA
Circuit protection
Current fuse (Near the terminal)
250 V, 25 A
Current fuse (Filter PCB)
250 V, 10 A
Current fuse (Main PCB)
250 V, 3.15 A
Fan motor
protection
Thermal protection
program
Activate
150±15 °C
Fan motor stop
Reset
120±15 °C
Fan motor restart
Compressor
protection
Terminal protection
program
(Compressor temp.)
Activate
108 °C
Compressor stop
Reset
After 40 minutes
Compressor restart
Thermal protection
program
(Discharge temp.)
Activate
110°C
Compressor stop
Reset
After 7 minutes
Compressor restart
High pressure
protection
Pressure switch
Activate
4.2±0.1 MPa
Compressor stop
Reset
3.2±0.15 MPa
Compressor restart