SERVICE PARTS INFORMATION 2
Check Point 1 : Check Connection
U
U
(RED)
(RED)
V
V
(WHITE)
(WHITE)
W
W
(BLACK)
(BLACK)
Terminal cover opened
MAIN PCB
Check Point 2 : Check Winding Resistance
Check Point 3 : Replace Main PCB
U
V
W
W304
(TM304)
W305
(TM305)
W303
(TM303)
RED
WHITE
BLACK
Compressor
Inverter Compressor
Check terminal connection of Compressor
(loose or incorrect wiring)
Check connection of Main PCB
(Loose or incorrect wiring)
Check winding resistance of each terminal
If the resistance value is 0 or infinite, replace Compressor.
If the symptom does not change with above Check 1, 2, replace Main PCB.
Resistance Value :
1.41 (For AU*24LUAR)
0.88 (For AU*30/ 36LUAS)
0.188 (For AU*45/ 54LUAS)
at 20°C
07-30
Summary of Contents for AO*24LMAKL
Page 5: ...1 SPECIFICATIONS R410A CASSETTE type INVERTER ...
Page 11: ...2 DIMENSIONS R410A CASSETTE type INVERTER ...
Page 15: ...3 REFRIGERANT SYSTEM DIAGRAM R410A CASSETTE type INVERTER ...
Page 19: ...4 CIRCUIT DIAGRAM R410A CASSETTE type INVERTER ...
Page 25: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A CASSETTE type INVERTER ...
Page 47: ...6 REFRIGERANT CAUTION R410A R410A CASSETTE type INVERTER ...
Page 56: ...7 TROUBLE SHOOTING R410A CASSETTE type INVERTER ...
Page 91: ...8 APPENDING DATA R410A CASSETTE type INVERTER ...
Page 110: ...9 INSTALLATION MANUAL R410A CASSETTE type INVERTER ...
Page 117: ...10 REPLACEMENT PARTS R410A CASSETTE type INVERTER ...
Page 158: ...10 41 8 DRAIN PAN removal Remove the DRAIN PAN ASSY DRAIN PAN ASSY ...
Page 162: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Apr 2006 Printed in Japan ...