When the outdoor heat exchanger temperature is lower than Operation temperature (Refer to Table 8) and the heating
operation has been stopped for 3 hours, power is applied to the compressor and the compressor is heated.
(By heating the compressor, warm air is quickly discharged when operation is started.)
When operation was started, and when the outdoor temperature rises to Release temperature or greater,
preheating is over.
5-16. COMPRESSOR PREHEATING
(Table 8 : Preheating Operation / Release Temperature)
05-14
5-15. PUMP DOWN ( For AU*30/ 36/ 45/ 54LUAS )
When the product is stopped:
1. Press the PUMP DOWN switch (SW2) on the outdoor unit.
(The LED on the outdoor unit circuit board flickers every 1second.)
2. The pump down operation (cooling operation) begins right away.
After operation starts, close the 3-way valve (liquid).
3. After 2-3minutes, operation stops. Close the 3-way valve (gas) within 1minute after operations stops.
4. The LED will go out 3minutes after it stops. Disconnect the power supply after confirming that the LED has gone out.
When the product is operating:
1. Press the PUMP DOWN switch (SW2) on the outdoor unit. The LED on the outdoor unit circuit board flickers
every 1second, and operation stops.
At this point, recovery has not been completed, so do not close the 2 and 3-way valves.
2. The pump down operation (cooling operation) begins after 3minutes.
Close the 3-way valve (liquid) after operation starts.
3. After 2-3minutes, operation stops. Close the 3-way valve (gas) within 1minute after operations stops.
4. The LED will go out 3minutes after it stops. Disconnect the power supply after confirming that the LED has gone out.
Perform the following procedures to collect the refrigerant when moving the indoor unit or the outdoor unit.
Before 24 hour
After 24 hour
Operation
temperature
Operation
temperature
Release
temperature
Release
temperature
3
°
C
7
°
C
0
°
C
4
°
C
Summary of Contents for AO*24LMAKL
Page 5: ...1 SPECIFICATIONS R410A CASSETTE type INVERTER ...
Page 11: ...2 DIMENSIONS R410A CASSETTE type INVERTER ...
Page 15: ...3 REFRIGERANT SYSTEM DIAGRAM R410A CASSETTE type INVERTER ...
Page 19: ...4 CIRCUIT DIAGRAM R410A CASSETTE type INVERTER ...
Page 25: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A CASSETTE type INVERTER ...
Page 47: ...6 REFRIGERANT CAUTION R410A R410A CASSETTE type INVERTER ...
Page 56: ...7 TROUBLE SHOOTING R410A CASSETTE type INVERTER ...
Page 91: ...8 APPENDING DATA R410A CASSETTE type INVERTER ...
Page 110: ...9 INSTALLATION MANUAL R410A CASSETTE type INVERTER ...
Page 117: ...10 REPLACEMENT PARTS R410A CASSETTE type INVERTER ...
Page 158: ...10 41 8 DRAIN PAN removal Remove the DRAIN PAN ASSY DRAIN PAN ASSY ...
Page 162: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Apr 2006 Printed in Japan ...