Trouble shooting 8
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Indoor Unit : No LED
Outdoor Unit : LED 2 times blink
ERROR CODE : E : 0C
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 :
Check Point 3 :
18.1
26.9
20°C
41.1
64.5
81.8
105
135
176
Resistance Value (k )
15°C
10°C
5°C
0°C
Temperature
OK
OK
OK
OK
12.5
30°C
50°C
40°C
60°C
0.51
180°C
0.77
160°C
1.21
1.98
3.43
4.61
6.31
8.78
Resistance Value (k )
140°C
120°C
100°C
90°C
80°C
70°C
Temperature
TH
ER
M
IS
TO
R
(D
IS
C
H
A
R
G
E)
TH
E
R
M
IS
TO
R
(P
IP
E
)
TH
E
R
M
IS
TO
R
(O
U
TD
O
O
R
)
TH
E
R
M
IS
TO
R
(C
O
M
P
R
E
S
S
O
R
)
TH
E
R
M
IS
TO
R
(H
E
A
T
S
IN
K
)
B
R
O
W
N
B
LA
C
K
B
LA
C
K
B
LU
E
B
R
O
W
N
CN21
CN22 CN23 CN26 CN25
1 2
1 2
1 2
1 2
1 2
Outdoor Discharge Pipe Temperature
Sensor Error
Outdoor Unit Main PCB Circuit
Discharge Pipe Temperature Thermistor
When Discharge Pipe Temperature Thermistor open or short-circuit
is detected at power ON or while running the compressor.
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.
07-11
Summary of Contents for AO*24LMAKL
Page 5: ...1 SPECIFICATIONS R410A CASSETTE type INVERTER ...
Page 11: ...2 DIMENSIONS R410A CASSETTE type INVERTER ...
Page 15: ...3 REFRIGERANT SYSTEM DIAGRAM R410A CASSETTE type INVERTER ...
Page 19: ...4 CIRCUIT DIAGRAM R410A CASSETTE type INVERTER ...
Page 25: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A CASSETTE type INVERTER ...
Page 47: ...6 REFRIGERANT CAUTION R410A R410A CASSETTE type INVERTER ...
Page 56: ...7 TROUBLE SHOOTING R410A CASSETTE type INVERTER ...
Page 91: ...8 APPENDING DATA R410A CASSETTE type INVERTER ...
Page 110: ...9 INSTALLATION MANUAL R410A CASSETTE type INVERTER ...
Page 117: ...10 REPLACEMENT PARTS R410A CASSETTE type INVERTER ...
Page 158: ...10 41 8 DRAIN PAN removal Remove the DRAIN PAN ASSY DRAIN PAN ASSY ...
Page 162: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Apr 2006 Printed in Japan ...