Trouble shooting 13
INDOOR UNIT
OUTDOOR UNIT Error Method:
Indicate or Display:
Indoor Unit : No LED
Outdoor Unit : LED 9 times blink/ 8 times blink(AU*24LMAKL)
ERROR CODE : E : 16
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 3 :
Check Point 2 : Check voltage of Main PCB (DC5.0V)
HIGH PRESSURE SW
BLACK
BLACK
RED
RED
CN37
1
2
1
2
3
4WV
OK
Check Point 1 :
Reset Power Supply and operate
Check Point 3 : Check Pressure Switch
YES
YES
NO
NO
Pressure Switch Error
Outdoor Unit Main PCB Circuit
Pressure Switch
1. Connector connection failure 2. Pressure Switch failure 3. Main PCB failure
When pressure switch open is detected in 10 seconds
after the power is turned on.
Does abnormal LED indication show again?
Make sure circuit diagram of outdoor unit and check terminal voltage
at Pressure Switch. (DC5.0V)
If the voltage does not appear, replace Main PCB.
Check if connector is loose or cable is open.
>> If no abnormal connection is found,
replace Pressure Switch.
After replacing Pressure Switch, check operating
condition and pressure in operation.
07-16
Summary of Contents for AO*24LMAKL
Page 5: ...1 SPECIFICATIONS R410A CASSETTE type INVERTER ...
Page 11: ...2 DIMENSIONS R410A CASSETTE type INVERTER ...
Page 15: ...3 REFRIGERANT SYSTEM DIAGRAM R410A CASSETTE type INVERTER ...
Page 19: ...4 CIRCUIT DIAGRAM R410A CASSETTE type INVERTER ...
Page 25: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A CASSETTE type INVERTER ...
Page 47: ...6 REFRIGERANT CAUTION R410A R410A CASSETTE type INVERTER ...
Page 56: ...7 TROUBLE SHOOTING R410A CASSETTE type INVERTER ...
Page 91: ...8 APPENDING DATA R410A CASSETTE type INVERTER ...
Page 110: ...9 INSTALLATION MANUAL R410A CASSETTE type INVERTER ...
Page 117: ...10 REPLACEMENT PARTS R410A CASSETTE type INVERTER ...
Page 158: ...10 41 8 DRAIN PAN removal Remove the DRAIN PAN ASSY DRAIN PAN ASSY ...
Page 162: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Apr 2006 Printed in Japan ...