Summary of R407C and R410A characteristics
Pressure (Mpa) Temp ( C)
2.20
37.9
2.25
38.7
2.30
39.6
2.35
40.5
2.40
41.3
2.45
42.1
2.55
43.8
2.60
44.6
2.65
45.3
2.70
46.1
2.75
46.8
2.80
47.6
2.85
48.3
2.90
49.0
2.95
49.8
3.00
50.5
3.05
51.2
3.10
51.9
3.15
52.6
3.20
53.2
3.25
53.9
3.30
54.6
3.35
55.3
3.40
55.9
3.45
56.5
3.50
57.1
2.55
57.8
3.60
58.4
3.65
59.0
3.70
59.6
3.75
60.2
3.80
60.8
3.85
61.4
3.90
52.0
3.95
62.5
4.00
63.1
4.05
63.6
4.10
64.2
4.15
64.8
Temp ( C) Pressure (Mpa)
39
2.27
40
2.32
41
2.38
42
2.44
44
2.57
45
2.63
46
2.69
47
2.76
48
2.83
49
2.90
51
3.04
52
3.11
53
3.18
54
3.26
56
3.41
57
3.49
58
3.57
59
3.65
61
3.82
62
3.90
63
3.99
64
4.08
Desighed pressure of R410A refrigerant
< Pressure Temp >
Relation between R410A condensing temperature and saturated pressure.
< Temp Pressure >
Advantage
Disadvantage
Suitable for
R410A
higher system
performance
Near-Azeotropic
refrigerant
1.6 times higher
(difficult to design against
pressure resistance)
Small Air-Conditioners
pressure than R22
R407C
similar pressure as R22
(possible to design
large equipment)
Zeotropic refrigerant
(handle with care)
Large Air-Conditioners
*
05-07
Summary of Contents for AO*24LMAKL
Page 5: ...1 SPECIFICATIONS R410A CASSETTE type INVERTER ...
Page 11: ...2 DIMENSIONS R410A CASSETTE type INVERTER ...
Page 15: ...3 REFRIGERANT SYSTEM DIAGRAM R410A CASSETTE type INVERTER ...
Page 19: ...4 CIRCUIT DIAGRAM R410A CASSETTE type INVERTER ...
Page 25: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A CASSETTE type INVERTER ...
Page 47: ...6 REFRIGERANT CAUTION R410A R410A CASSETTE type INVERTER ...
Page 56: ...7 TROUBLE SHOOTING R410A CASSETTE type INVERTER ...
Page 91: ...8 APPENDING DATA R410A CASSETTE type INVERTER ...
Page 110: ...9 INSTALLATION MANUAL R410A CASSETTE type INVERTER ...
Page 117: ...10 REPLACEMENT PARTS R410A CASSETTE type INVERTER ...
Page 158: ...10 41 8 DRAIN PAN removal Remove the DRAIN PAN ASSY DRAIN PAN ASSY ...
Page 162: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Apr 2006 Printed in Japan ...