Check Point 2 :
Check Point 2 : Check Connector (CN15) / Wire
Check Point 1 : Check Float Switch
Check Point 3 : Replace Controller PCB
ON
ON
OFF
OFF
OK
OK
OK
OK
Trouble shooting 6
INDOOR UNIT Error Method:
Indicate or Display:
Indoor Unit : No LED
Outdoor Unit : No indication
ERROR CODE : E : 09
Detective Actuators:
Detective details:
Forecast of Cause :
Water Drain Abnormal
Indoor Unit Controller PCB Circuit
Float Switch
When Float Switch is ON for more than 3 minutes.
1. Float Switch failure 2. Shorted connector/ wire 3. Controller PCB failure
Check operation of float switch. (any blocking by dust, etc.)
Remove Float switch and check ON/OFF switching operation
by using a meter.
>>If Float switch is detective, replace it.
Check loose contact of CN15 /shorted wire (pinched wire).
>>Replace Float switch if the wire is abnormal
If Check Point 1 & 2 do not improve the symptom, change Controller PCB.
07-09
Summary of Contents for AO*24LMAKL
Page 5: ...1 SPECIFICATIONS R410A CASSETTE type INVERTER ...
Page 11: ...2 DIMENSIONS R410A CASSETTE type INVERTER ...
Page 15: ...3 REFRIGERANT SYSTEM DIAGRAM R410A CASSETTE type INVERTER ...
Page 19: ...4 CIRCUIT DIAGRAM R410A CASSETTE type INVERTER ...
Page 25: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A CASSETTE type INVERTER ...
Page 47: ...6 REFRIGERANT CAUTION R410A R410A CASSETTE type INVERTER ...
Page 56: ...7 TROUBLE SHOOTING R410A CASSETTE type INVERTER ...
Page 91: ...8 APPENDING DATA R410A CASSETTE type INVERTER ...
Page 110: ...9 INSTALLATION MANUAL R410A CASSETTE type INVERTER ...
Page 117: ...10 REPLACEMENT PARTS R410A CASSETTE type INVERTER ...
Page 158: ...10 41 8 DRAIN PAN removal Remove the DRAIN PAN ASSY DRAIN PAN ASSY ...
Page 162: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Apr 2006 Printed in Japan ...