2. HEATING OPERATION
2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is lower by 3 C than a set temperature, the compressor operation
frequency will attain to maximum performance.
* If the room temperature is higher 2.5 C than a set temperatire, the compressor will be
stopped.
minimum
frequency
maximum
frequency
AS*9LSACW
18Hz
130Hz
AS*12LSACW
18Hz
130Hz
AS*9LSBCW
18Hz
130Hz
AS*12LSBCW
18Hz
130Hz
AS*14LSBCW
18Hz
119Hz
AS*18LSBCW
18Hz
119Hz
Outside air Outside air
temperature temperature
19 C
C zone
17 C
14 C
B zone
12 C
A zone
Hi
Me
Lo
Quiet
A zone
130Hz
92Hz
80Hz
68Hz
B zone
130Hz
80Hz
60Hz
54Hz
9LSACW
C zone
96Hz
68Hz
54Hz
51Hz
A zone
130Hz
96Hz
80Hz
68Hz
B zone
130Hz
96Hz
64Hz
57Hz
12LSACW
C zone
96Hz
96Hz
64Hz
54Hz
A zone
130Hz
96Hz
80Hz
68Hz
B zone
130Hz
96Hz
80Hz
54Hz
9LSBCW
C zone
130Hz
96Hz
80Hz
45Hz
A zone
130Hz
96Hz
80Hz
68Hz
B zone
130Hz
96Hz
80Hz
54Hz
12LSBCW
C zone
130Hz
96Hz
80Hz
45Hz
A zone
119Hz
90Hz
70Hz
58Hz
B zone
119Hz
90Hz
70Hz
58Hz
14LSBCW
C zone
119Hz
90Hz
70Hz
58Hz
A zone
119Hz
90Hz
70Hz
58Hz
B zone
119Hz
90Hz
70Hz
58Hz
18LSBCW
C zone
119Hz
90Hz
70Hz
58Hz
* When the room temperature is b2 C to -3 C of the setting temperature,
the compressor frequency is controlled within the range shown in Table2.
However, the maximum frequency is limited in the range shown in Figure 2 based on the
fan speed mode and the outdoor temperature.
( Table 2 : Compressor Frequency Range )
( Fig.2 : Limit of Maximum Frequency based on Outdoor Temperature )
* The room temperature is controlled 2 C higher than the setting temperature for 60 minutes
after starting the operation.
After 60 minutes, it is controlled based on the normal setting temperature.
05-02
Summary of Contents for AO*12LFBC
Page 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 12: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 16: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 20: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 40: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Page 46: ......
Page 47: ......
Page 70: ...9 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Page 83: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS17032005 March 2005 Printed in Japan ...