2. PRECAUTION FOR INSTALLATION
Precaution for installation
Selection of pipe
Pipe thickness
Outer diameter
Thickness
1/4”
(6.35mm)
0.8 mm
3/8” (9.52mm)
0.8 mm
1/2” (12.7mm)
0.8 mm
Be sure to use this pipe thickness and over
for countermeasure against higher
pressure.
Flare and flare nuts
Diameter 1/4”(6.35mm) 3/8”(9.52mm) 1/2”(12.7mm)
Refrigerant
R410A
R22
/R407C
R410A
R410A
A
9.1
9.0
13.2
13.0
16.6
16.2
B
13
12
20
15
13
20
C
12
11
16
12.5
19
16
Nut width
17
22
26
24
Always use the flare nut that is packed
with the product.
Do not use existing (for R22) pipes
• Be sure to use new pipes when replacing
conventional (R22) model with
HFC
(R407C, R410A)
model.
• If you use existing pipes, it may cause
resolution of compressor oil by remaining
mineral oil.
R22
/R407C
R22
/R407C
06-02