Defrost Flow Chart
The defrosting shall proceed by the integrating operation time and outdoor heat exchanger
temperature as follows.
(Not defrosted for 10 minutes)
(In case of 1st defrost)
(In case of 2nd and later defrost)
Compressor OFF
Outdoor fan motor OFF
30 sec later four - way valve OFF
36 sec later compressor ON
Heating operation start : Compressor ON
Compressor integrating
operation:
Over 20 minutes to
below 60 minutes
Compressor integrating
operation:
Over 60 minutes to
below 240 minutes
Compressor integrating
operation:
Over 240 minutes
Compressor integrating
operation:
Over 35 minutes to
below 240 minutes
Compressor integrating
operation:
Over 240 minutes
Outdoor heat exchanger
temperature:
Below - 9 C
Outdoor heat exchanger
temperature:
Outdoor heat exchanger
temperature:
Outdoor heat exchanger
temperature:
Outdoor heat exchanger
temperature:
Defrost start
Defrost Indicator:
[Operation lamp]
7 sec ON / 2 sec OFF
Outdoor heat exchanger temperature:
Over 10 C / 16 C
or
Compressor ON time:
Over 15 minutes
Defrost end
Below - 5 C
Below - 3 C
Below - 6 C
Below - 3 C
05-15
Summary of Contents for AO*12LFBC
Page 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 12: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 16: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 20: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 40: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Page 46: ......
Page 47: ......
Page 70: ...9 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Page 83: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS17032005 March 2005 Printed in Japan ...