Active Filter Failure
[Checking points]
Check the following points and locae the cause in the outdoor unit.
[Cause]
(1) Incorrect wiring
(2) Active Filter Module defective
(3) PC Board defective
(4) DC voltage detectiion circuit defective
[First Step]
Measure the DC voltage at terminals (between Electrolytic Capacitor and discharge resistance)
in the Inverter Controller Assy, and make sure it is lower than DC5V.
If it is higher than 5V, wait until the discharging is over.
Open the Inverter Controller Assy
and check if there is abnormal points.
Incorrect wiring > Correct and recheck
(Incorrect wiring, Parts touched, Parts broken)
Parts touched > Correct and recheck
Parts broken > Change the broken part
Turn on the power and press TEST button
on Remote Control.
Is the outdoor fan rotating?
Operate the unit for certain time and
measure the terminal voltage of the
The unit is normal.
discharge resistance.
Is the DC voltage between 350 to 425V?
Recheck
Operate the unit for certain time and
Yes(Operating) >
Check completed
check if the compressor is operating.
No(Not operating) > Return to the start
Check point (1)
Yes(Normal)
Go to Check point (2)
No(Abnormal)
Check point (2)
Yes(Rotating)
Go to Check point (3)
No(Not rotating)
Check point (3)
Yes(Within range)
No(Out of range)
ACTPM or PCB defective > Replace Main PCB
ACTPM or PCB defective > Replace ACTPM or
Main PCB.
(Replace only ACTPM if Main PCB was replaced
at Check point (2).)
07-10
Summary of Contents for AO*12LFBC
Page 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 12: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 16: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 20: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 40: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Page 46: ......
Page 47: ......
Page 70: ...9 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Page 83: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS17032005 March 2005 Printed in Japan ...