IPM Protection
[Checking Points]
Check the following points and locae the cause in the outdoor unit.
[Cause]
(1) Compressor failure
(2) Refrigeration cycle failure
(3) PC Board defective
(4) IPM defective
(5) Incorrect wiring
[First step]
Measure the DC voltage at terminals (between Electrolytic Capacitor and discharge resistance)
in the Inverter Controller Assy, and make sure it is lower than DC5V.
Check point (1)
Open the Inverter Controller Assy
Yes(Normal)
Go to Check point (2)
and check if there is abnormal points.
No(Abnormal)
Incorrect wiring > Correct and recheck
Parts touched > Correct and recheck
Parts broken > Change the broken part
Check point (2)
Turn on the power and press TEST button
Yes(Rotating)
Go to Check point (3)
on Remote Control.
No(Not rotating)
IPM or PCB defective > Replace PCB
Is the outdoor fan rotating?
Check point (3)
Operate the unit for certain time and
Yes(Operating)
The unit is normal.
check if the compressor is operating.
No(Not operating)
IPM or PCB defective > Replace PCB
Recheck
Operate the unit for certain time and
Yes(Operating) > Check completed
check if the compressor is operating.
No(Not operating) > Return to the start
If it is higher than 5V, wait until the discharging is over.
07-09
Summary of Contents for AO*12LFBC
Page 4: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Page 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Page 12: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 16: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Page 20: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Page 40: ...6 REFRIGERANT CAUTION R410A R410A WALL MOUNTED type INVERTER ...
Page 46: ......
Page 47: ......
Page 70: ...9 INSTALLATION MANUAL R410A WALL MOUNTED type INVERTER ...
Page 83: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan GS17032005 March 2005 Printed in Japan ...