Setting Mode
ITEM
CODE No.
Setting Function
Default
Indoor unit field setting
Address
setting by
remote controller
01
Indoor unit address
00~63
00~63
00
02
Refrigerant circuit address
00~99
00~99
00
Filter
11
Filter indicator Interval
00
Default
01
Longer
02
Shorter
13
Filter sign display
00
Enable
01
Disable
02
Display only on central remote control
Airflow
20
Ceiling airflow
00
Default
(Cassette type only)
01
High ceiling
23
Vertical airflow direction
00
Default
01
Raise
24
Horizontal swing airflow direction
00
Default
01
Left half
02
Right half
Correction
30
Cool air temperature trigger
00
Default (0
°C)
01
Temperature overshoot setting (+2
°C)
02
Temperature undershoot setting (-2
°C)
31
Heat air temperature trigger
00
Default (0
°C)
01
Temperature undershoot setting (-6
°C)
02
Temperature slightly undershoot setting (-4
°C)
03
Temperature overshoot setting (+4
°C)
Change of
40
Auto restart
00
Enable
01
Disable
43
Cool air prevention
00
Enable
01
Disable (Ventilation mode)
46
External control
00
Start / Stop
01
Emergency stop
47
Error report target
00
All
01
Display only for central remote control
Install
00
Pipe length setting
00
40-65m
Setting mode
01
0-40m
02
65-90m
03
90-120m
04
120-150m
Correction
10
Sequential start shift
00
01
21sec. Delay
02
42sec. Delay
03
63sec. Delay
11
Cooling capacity shift
00
Normal mode
01
Save energy mode 1 (+2
°C)
02
High power mode 1 (-2
°C)
03
High power mode 2 (-4
°C)
12
Heating capacity shift
00
Normal mode
01
Save energy mode (-2
°C)
02
High power mode 1 (+2
°C)
03
High power mode 2 (+4
°C)
13
Defrost setting shift
00
End temperature:Normal
01
End temperature:Higher
01
Emergency stop
21
Operation mode selecting method
00
Priority given to the first command
01
Priority given to the external input of outdoor unit
02
Priority given to the master indoor unit
22
Snow falling protection fan mode
00
Normal operation
01
Snow falling protection fan mode
23
Interval setting for snow falling
00
Standard (30min)
01
Short 1 (5min)
02
Short 2 (10min)
03
Short 3 (20min)
24
High static pressure mode
00
Standard
01
High static pressure 1 (equivalent to 30Pa)
02
High static pressure 2 (equivalent to 80Pa)
28
Change of unit (Temperature)
00
Celsius(
°C)
01
Fahrenheit ( F)
29
Change of unit (Pressure)
00
MPa
01
psi
Change of
Change of
function 3
30
Energy saving level setting
00
Level 1 (stop)
01
Level 2 (operated at 40% capacity)
02
Level 3 (operated at 60% capacity)
03
Level 4 (operated at 80% capacity)
04
Level 5 (operated at 100% capacity)
Low noise
40
Capacity priority setting
00
Off (quiet priority)
01
On (capacity priority)
41
Low noise mode setting
00
Off (Normal)
60
Back up operation
00
*1
On
01
*2
Off
01
On (Low noise mode operation is always done)
42
Low noise mode operation
00
Level 1 (55dB)
01
Level 2 (50dB)
[ F2 ]
ITEM
CODE No.
Normal
20
Switching between forced stop or
00
Forced stop
Change of
function 1
emergency stop
protection fan mode
setting 1
(in low noise mode)
level setting
function 2
Function 1
Classification
01-12
Push switch on
outdoor unit PCB
*1 : If one of compressor fails, backup operation will be performed by the remaining compressors.
*2 : If one of compressor fails, all units will be abnormal stop.
Summary of Contents for AIRSTAGE V-II
Page 2: ......
Page 6: ...1 TEST RUN ...
Page 7: ......
Page 22: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 23: ......
Page 39: ...3 INDOOR UNIT OPERATION ...
Page 40: ......
Page 59: ...4 TROUBLE SHOOTING ...
Page 60: ......
Page 187: ...5 APPENDING DATA UNIT ...
Page 188: ......
Page 193: ...MODELS AUXB07 AUXB09 AUXB12 AUXB14 AUXB18 AUXB24 05 05 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit ...
Page 194: ...MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 05 06 ...
Page 195: ...MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 05 07 ...
Page 196: ...MODEL ARXB24 MODELS ARXB30 ARXB36 05 08 ...
Page 197: ...MODEL ARXB45 05 09 ...
Page 198: ...MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 05 10 ...
Page 199: ...MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 05 11 ...
Page 200: ...MODELS ARXD07 ARXD09 ARXD12 ARXD14 ARXD18 ARXD24 05 11 1 ...
Page 201: ...MODELS AB A12 AB A14 AB A18 AB A24 05 12 ...
Page 202: ...MODELS AB A12LBTH AB A14LBTH 05 12 1 AB A18LBTH AB A24LBTH ...
Page 203: ...05 13 MODELS AB A30 AB A36 AB A45 AB A54 ...
Page 204: ...05 13 1 MODELS AB A30LBTH AB A36LBTH AB A45LBTH AB A54LBTH ...
Page 205: ...MODELS AS A07 AS A09 AS A12 AS A14 05 14 ...
Page 206: ...MODELS AS E07 AS E09 AS E12 AS E14 05 15 ...
Page 207: ...MODELS AS A18 AS A24 AS A30 05 16 ...
Page 208: ...05 16 1 MODELS AS A18LACH AS A24LACH AS A30LACH ...
Page 216: ...6 DISASSEMBLY PROCESS ...
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 225: ......
Page 226: ......