Trouble shooting 63
Indoor Unit - No Power
Forecast of Cause :
1. Power Supply failure 2. Outside cause 3. Electrical Component defective
Check Point 1 : Check Installation Condition
Is not the breaker down?
Check loose or removed connection cable.
>>If abnormal condition is found, correct it by referring to
Installation Manual or Data & Technical Manual.
Check Point 3 : Check Electrical Components
Check Point 2 : Check Outside Cause such as Voltage drop or Noise
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line (Neon bulb or electric equipment that may
cause harmonic wave).
Check the complete insulation of grounding.
Check the fuse and thermal fuse.
OK
NG
Replace the fuse or thermal fuse.
Check if the power supply terminals section is shorted.
NG
OK
OK
TROUBLE SHOOTING WITH NO ERROR CODE
Check Voltage of power supply.
>> Check AC220V appears at Indoor Unit Terminal 1 - 2 (Power Supply).
AC
For AS model, advance to OK without checking.
For models other than the AS model, disconnect the cable connecting
the Power Supply PCB and controller PCB and recheck if the power supply terminals
section is not shorted.
(Note) Always check in the power off state.
NG
OK
NG
Replace the controller PCB.
(Refer to 06-03 page Main PCB removal.)
Replace the Power Supply PCB.
OK
NG
Replace the Display PCB.
NG
OK
OK
04-70
If the symptom does not change by above Check 3, replace Controller PCB or Power Supply PCB.
>>If replace Controller PCB, Refer to 06-03 page Main PCB removal.
Summary of Contents for AIRSTAGE V-II
Page 2: ......
Page 6: ...1 TEST RUN ...
Page 7: ......
Page 22: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 23: ......
Page 39: ...3 INDOOR UNIT OPERATION ...
Page 40: ......
Page 59: ...4 TROUBLE SHOOTING ...
Page 60: ......
Page 187: ...5 APPENDING DATA UNIT ...
Page 188: ......
Page 193: ...MODELS AUXB07 AUXB09 AUXB12 AUXB14 AUXB18 AUXB24 05 05 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit ...
Page 194: ...MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 05 06 ...
Page 195: ...MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 05 07 ...
Page 196: ...MODEL ARXB24 MODELS ARXB30 ARXB36 05 08 ...
Page 197: ...MODEL ARXB45 05 09 ...
Page 198: ...MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 05 10 ...
Page 199: ...MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 05 11 ...
Page 200: ...MODELS ARXD07 ARXD09 ARXD12 ARXD14 ARXD18 ARXD24 05 11 1 ...
Page 201: ...MODELS AB A12 AB A14 AB A18 AB A24 05 12 ...
Page 202: ...MODELS AB A12LBTH AB A14LBTH 05 12 1 AB A18LBTH AB A24LBTH ...
Page 203: ...05 13 MODELS AB A30 AB A36 AB A45 AB A54 ...
Page 204: ...05 13 1 MODELS AB A30LBTH AB A36LBTH AB A45LBTH AB A54LBTH ...
Page 205: ...MODELS AS A07 AS A09 AS A12 AS A14 05 14 ...
Page 206: ...MODELS AS E07 AS E09 AS E12 AS E14 05 15 ...
Page 207: ...MODELS AS A18 AS A24 AS A30 05 16 ...
Page 208: ...05 16 1 MODELS AS A18LACH AS A24LACH AS A30LACH ...
Page 216: ...6 DISASSEMBLY PROCESS ...
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 225: ......
Page 226: ......