02-04
Normal control
End conditions
Normal control
Constant speed ON
30rps fixed
70rps fixed
70rps fixed
70rps fixed
(3) Limits the upper limit speed of the INV compressor according to the present high-pressure value.
(2) Heating starting process
At the start of heating, the compressor is started by the following process. All compressors start-up
to change the 4 way valve. Capacity control returns to normal control after the end of the starting process.
(target high-pressure control)
2 compressors outdoor unit (12, 14, 16HP)
1 compressor outdoor unit (8, 10HP)
Starting process
Starting process
Starting process
Starting process
Starting process
Starting process
7 minutes elapsed from start of process
or
1 minute elapsed from start of process and high-pressure of
all outdoor units 2.50MPa
Compression ratio of any outdoor unit 8
30 minutes elapsed from start of process
or
high-pressure of all outdoor units 2.63MPa
or
discharge SH of all operating compressors 12
[ a ] = 1.25 Low pressure value 2.125
High Pressure
3.80MPa
3.30MPa
(Maximum) 3.00MPa
Maximum speed = 80rps
Maximum speed = 90rps
Maximum speed = 95rps
Maximum speed = 100rps
[ a ]
< Starting process >
Inverter compressor of all outdoor unit is started at 40rps and normal control immediately begins.
(target high-pressure control)
*However, when the following condition (A) or (B) are satisfied, starting process is not performed.
< Conditions under which starting process is not performed >
(A) When outside air temperature 20°C
(B) When the starting process at heating before stopped at the start of heating
(including thermostat OFF stop) within 30 minutes after heating stopped.
< Operation >
Summary of Contents for AIRSTAGE V-II
Page 2: ......
Page 6: ...1 TEST RUN ...
Page 7: ......
Page 22: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 23: ......
Page 39: ...3 INDOOR UNIT OPERATION ...
Page 40: ......
Page 59: ...4 TROUBLE SHOOTING ...
Page 60: ......
Page 187: ...5 APPENDING DATA UNIT ...
Page 188: ......
Page 193: ...MODELS AUXB07 AUXB09 AUXB12 AUXB14 AUXB18 AUXB24 05 05 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit ...
Page 194: ...MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 05 06 ...
Page 195: ...MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 05 07 ...
Page 196: ...MODEL ARXB24 MODELS ARXB30 ARXB36 05 08 ...
Page 197: ...MODEL ARXB45 05 09 ...
Page 198: ...MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 05 10 ...
Page 199: ...MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 05 11 ...
Page 200: ...MODELS ARXD07 ARXD09 ARXD12 ARXD14 ARXD18 ARXD24 05 11 1 ...
Page 201: ...MODELS AB A12 AB A14 AB A18 AB A24 05 12 ...
Page 202: ...MODELS AB A12LBTH AB A14LBTH 05 12 1 AB A18LBTH AB A24LBTH ...
Page 203: ...05 13 MODELS AB A30 AB A36 AB A45 AB A54 ...
Page 204: ...05 13 1 MODELS AB A30LBTH AB A36LBTH AB A45LBTH AB A54LBTH ...
Page 205: ...MODELS AS A07 AS A09 AS A12 AS A14 05 14 ...
Page 206: ...MODELS AS E07 AS E09 AS E12 AS E14 05 15 ...
Page 207: ...MODELS AS A18 AS A24 AS A30 05 16 ...
Page 208: ...05 16 1 MODELS AS A18LACH AS A24LACH AS A30LACH ...
Page 216: ...6 DISASSEMBLY PROCESS ...
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 225: ......
Page 226: ......