(2) Target low-pressure and high-pressure control
In order to make the evaporation pressure of the indoor unit at the proper pressure on a variety of operations,
capacity of the compressor will be controlled by low-pressure sensor of the outdoor unit (Master unit).
In order to make the condensation pressure of the indoor unit at the proper pressure on a variety of operations,
capacity of the compressor will be controlled by high-pressure sensor of the outdoor unit (Master unit).
Target low-pressure and high pressure temperature depends on system capacity, capacity of compressor operation,
pipe length, and capacity shift switch settings.
<Cooling>
<Heating>
02-03
2-2-3
Speed Range of Start, Stop, And Operation
(For DC Inverter Rotary Compressor)
On stop mode : 0 rps
On operating mode : 30 - 100 rps
(1) Cooling starting process
For cooling operation only, the upper limit speed at starting is made 50rps and is raised in
+10rps increments every 60 seconds.
S
pe
ed
Time
0
50rps
60sec
Target speed
60
sec
60sec
60rps
70rps
80rps
60sec
120
sec
180
sec
240
sec
90rps
10rps
10rps
Master and slave inverter compressors rotational speed are controlled the same
( In the case of multi outdoor unit )
The compressor operates at the upper limit speed if the target speed is higher than the upper limit speed.
The compressor operates at the target speed if the target speed is lower than the upper limit speed.
60sec
10rps
Summary of Contents for AIRSTAGE V-II
Page 2: ......
Page 6: ...1 TEST RUN ...
Page 7: ......
Page 22: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 23: ......
Page 39: ...3 INDOOR UNIT OPERATION ...
Page 40: ......
Page 59: ...4 TROUBLE SHOOTING ...
Page 60: ......
Page 187: ...5 APPENDING DATA UNIT ...
Page 188: ......
Page 193: ...MODELS AUXB07 AUXB09 AUXB12 AUXB14 AUXB18 AUXB24 05 05 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit ...
Page 194: ...MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 05 06 ...
Page 195: ...MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 05 07 ...
Page 196: ...MODEL ARXB24 MODELS ARXB30 ARXB36 05 08 ...
Page 197: ...MODEL ARXB45 05 09 ...
Page 198: ...MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 05 10 ...
Page 199: ...MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 05 11 ...
Page 200: ...MODELS ARXD07 ARXD09 ARXD12 ARXD14 ARXD18 ARXD24 05 11 1 ...
Page 201: ...MODELS AB A12 AB A14 AB A18 AB A24 05 12 ...
Page 202: ...MODELS AB A12LBTH AB A14LBTH 05 12 1 AB A18LBTH AB A24LBTH ...
Page 203: ...05 13 MODELS AB A30 AB A36 AB A45 AB A54 ...
Page 204: ...05 13 1 MODELS AB A30LBTH AB A36LBTH AB A45LBTH AB A54LBTH ...
Page 205: ...MODELS AS A07 AS A09 AS A12 AS A14 05 14 ...
Page 206: ...MODELS AS E07 AS E09 AS E12 AS E14 05 15 ...
Page 207: ...MODELS AS A18 AS A24 AS A30 05 16 ...
Page 208: ...05 16 1 MODELS AS A18LACH AS A24LACH AS A30LACH ...
Page 216: ...6 DISASSEMBLY PROCESS ...
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 225: ......
Page 226: ......