SERVICE PARTS INFORMATION 1
Compressor
Does not start up
Diagnosis method of Compressor (If Outdoor Unit 7 segment LED displays Error, refer to Trouble shooting )
Replace Compressor
Is any Indoor Unit in operation?
* If it is operated right after stopping
operation, 3 minutes start-up protection
by differential pressure is kicked on.
Stops soon after starting up
Abnormal noise
Check power supply voltage,open
fuse.
Is there open or loose connection
cable?
Check power supply voltage,open
fuse.
Is there open or loose connection
cable?
In case of constant speed compressor, check connection
and winding resistance.(Check if Protector is operated) Refer to
the next page.
In case of inverter compressor, check Filter PCB, Inverter
PCB, connection of Compressor, and winding resistance. (Refer
to the next page).
>> If there is no failure, the defect of Compressor can be
considered. (Compression part broken or valve defective.)
In case of constant speed
compressor, check connection and
winding resistance.(Check if Protector
is operated) Refer to the next page.
In case of inverter compressor, check
Filter PCB, Inverter PCB, connection of
Compressor, and winding resistance
(Refer to the next page).
>> If there is no failure, the defect of
Compressor is considered (Locked
compressor due to clogged dirt or
less oil)
Replace Compressor
Check if Refrigerant is leaking.
(Recharge Refrigerant)
Isn’t it Liquid Compression?
>> Check Low pressure value and if
it too high, check Indoor Unit.
(Indoor Unit EEV too much open, or
Indoor unit EEV that is not in
operation open.
Replace Compressor
Check power supply
voltage,open fuse. Is there
open or loose connection
cable?
Defective Compressor
can be considered.
(due to inside dirt clogging
or broken component)
Is Gas Pipe Valve open?
(Low Pressure is too low)
Check if Strainer is clogged.
MPa MPa
4-5 SERVICE PARTS INFORMATION
04-98
Summary of Contents for AIRSTAGE V-II
Page 2: ......
Page 6: ...1 TEST RUN ...
Page 7: ......
Page 22: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 23: ......
Page 39: ...3 INDOOR UNIT OPERATION ...
Page 40: ......
Page 59: ...4 TROUBLE SHOOTING ...
Page 60: ......
Page 187: ...5 APPENDING DATA UNIT ...
Page 188: ......
Page 193: ...MODELS AUXB07 AUXB09 AUXB12 AUXB14 AUXB18 AUXB24 05 05 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit ...
Page 194: ...MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 05 06 ...
Page 195: ...MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 05 07 ...
Page 196: ...MODEL ARXB24 MODELS ARXB30 ARXB36 05 08 ...
Page 197: ...MODEL ARXB45 05 09 ...
Page 198: ...MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 05 10 ...
Page 199: ...MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 05 11 ...
Page 200: ...MODELS ARXD07 ARXD09 ARXD12 ARXD14 ARXD18 ARXD24 05 11 1 ...
Page 201: ...MODELS AB A12 AB A14 AB A18 AB A24 05 12 ...
Page 202: ...MODELS AB A12LBTH AB A14LBTH 05 12 1 AB A18LBTH AB A24LBTH ...
Page 203: ...05 13 MODELS AB A30 AB A36 AB A45 AB A54 ...
Page 204: ...05 13 1 MODELS AB A30LBTH AB A36LBTH AB A45LBTH AB A54LBTH ...
Page 205: ...MODELS AS A07 AS A09 AS A12 AS A14 05 14 ...
Page 206: ...MODELS AS E07 AS E09 AS E12 AS E14 05 15 ...
Page 207: ...MODELS AS A18 AS A24 AS A30 05 16 ...
Page 208: ...05 16 1 MODELS AS A18LACH AS A24LACH AS A30LACH ...
Page 216: ...6 DISASSEMBLY PROCESS ...
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 225: ......
Page 226: ......