Compressor 1 Tempreture Abnormal
OK
OK
OK
OK
1. 3-way valve not opened
2. EEV defective, strainer clogged
3. Outdoor unit operation defective, foreign matter on heat exchanger
4. Compressor 1 temperature thermistor defective
5. Insufficient refrigerant
Compressor temperature thermistor 1
Compressor 1 temperature thermistor characteristics check
(Check by disconnecting thermistor from PCB)
* For the characteristics of the thermistor, refer to the "Service Parts Information 22.
Check Point 4 : Check the compressor 1 temperature thermistor
Check Point 3 : Outdoor unit fan, heat exchanger chek
Check for foreign matter at heat exchanger
Check if fan can be rotated by hand.
Motor check
Check Point 5 : Check the refrigerant amount
Leak check
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E. A3. 1
Error Code : A3
04-62
<Cooling operation>
OK
<Heating operation>
Check Point 1 : Check if 3-way valve(gas side) is open.
EEV (EEV2, indoor unit EEV) open?
Strainer clogging check (before and after EEV, ACM
oil return)
Refer to "Service Parts Information 14, 16".
Check Point 2 : Check the EEV, strainer
EEV (EEV1, EEV2) open?
Strainer clogging check (before and after EEV, ACM
oil return)
Refer to "Service Parts Information 15, 16".
Check Point 2 : Check the EEV, strainer
If the 3-way valve(gas side) was closed, open the
3-way valve(gas side) and check operation.
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the
3-way valve(liquid side) and check operation.
OK
"Protection stop by "compressor 1 tempreture" 112 during compressor 1
operation""generated 2 times within 40 minutes
Trouble shooting 54
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
After fixing the problem and for canceling the Error, Error Reset (F3-40) will be required after power reset
Summary of Contents for AIRSTAGE V-II
Page 2: ......
Page 6: ...1 TEST RUN ...
Page 7: ......
Page 22: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Page 23: ......
Page 39: ...3 INDOOR UNIT OPERATION ...
Page 40: ......
Page 59: ...4 TROUBLE SHOOTING ...
Page 60: ......
Page 187: ...5 APPENDING DATA UNIT ...
Page 188: ......
Page 193: ...MODELS AUXB07 AUXB09 AUXB12 AUXB14 AUXB18 AUXB24 05 05 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit ...
Page 194: ...MODELS AUXD18 AUXD24 AUXA30 AUXA36 AUXA45 AUXA54 05 06 ...
Page 195: ...MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 05 07 ...
Page 196: ...MODEL ARXB24 MODELS ARXB30 ARXB36 05 08 ...
Page 197: ...MODEL ARXB45 05 09 ...
Page 198: ...MODEL ARXA24 MODELS ARXA30 ARXA36 ARXA45 05 10 ...
Page 199: ...MODELS ARXC36 ARXC45 ARXC60 MODELS ARXC72 ARXC90 05 11 ...
Page 200: ...MODELS ARXD07 ARXD09 ARXD12 ARXD14 ARXD18 ARXD24 05 11 1 ...
Page 201: ...MODELS AB A12 AB A14 AB A18 AB A24 05 12 ...
Page 202: ...MODELS AB A12LBTH AB A14LBTH 05 12 1 AB A18LBTH AB A24LBTH ...
Page 203: ...05 13 MODELS AB A30 AB A36 AB A45 AB A54 ...
Page 204: ...05 13 1 MODELS AB A30LBTH AB A36LBTH AB A45LBTH AB A54LBTH ...
Page 205: ...MODELS AS A07 AS A09 AS A12 AS A14 05 14 ...
Page 206: ...MODELS AS E07 AS E09 AS E12 AS E14 05 15 ...
Page 207: ...MODELS AS A18 AS A24 AS A30 05 16 ...
Page 208: ...05 16 1 MODELS AS A18LACH AS A24LACH AS A30LACH ...
Page 216: ...6 DISASSEMBLY PROCESS ...
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 225: ......
Page 226: ......