6-1. Defrost operation in heating operation stopped
If the outdoor unit is frosted when stopping the heating operation, it stops after performing the auto-
matic defrosting operation.
In this time, if the indoor unit operation lamp flashes slowly (6 sec on/2 sec off), the outdoor unit al-
low the heat exchanger to defrost, and then stop.
•
Triggering condition
When all of the following conditions are satisfied in heating operation
– Compressor operation integrating time: 30 minutes or more
– Compressor continuous operation time: 10 minutes or more
– Outdoor unit heat exchanger temperature: -4°C or less
•
Release condition
The defrost operation is released when either one of the conditions below is satisfied.
Outdoor unit heat exchanger temperature
(after 1 minute or later since compressor start)
16°C or more
Compressor operation time
15 minutes
6-1. Defrost operation in heating operation stopped
- (04-24) -
6. Defrost operation control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for AGYG09KVCB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 10 05 SR_CH01_AG002EF_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 25 SR_CH02_AG002EF_02 ...
Page 37: ...3 TROUBLESHOOTING 2020 11 11 SR_CH03_AG002EF_01 ...
Page 39: ...5 1 Indoor unit 03 44 5 2 Outdoor unit 03 45 CONTENTS continued ...
Page 40: ......
Page 87: ...4 CONTROL AND FUNCTIONS 2020 11 11 SR_CH04_AG002EF_01 ...
Page 121: ...5 FILED WORKING 2020 11 11 SR_CH05_AG002EF_01 ...