1-4. Compressor frequency at normal start-up
¢
Model: AOYG09KVCBN
Compressor frequency soon after starting is controlled as below.
Frequency I
Frequency II
Frequency III
Frequency IV
Frequency V
Time 1
Time 2
Time 3
Time 4
Time 5
Frequency (rps)
I
II
III
IV
V
40
56
77
90
99
Time (sec)
1
2
3
4
5
60
240
280
360
400
¢
Models: AOYG12KVCBN and AOYG14KVCBN
Compressor frequency soon after starting is controlled as below.
Frequency I
Frequency II
Frequency III
Frequency IV
Frequency V
Frequency VI
Time 1
Time 2
Time 3
Time 4
Time 5
Time 6
Frequency
(rps)
I
II
III
IV
V
VI
35
52
64
71
89
97
Time (sec)
1
2
3
4
5
6
60
140
170
200
350
410