2-23. E: A8. Refrigerant leakage sensor error (Indoor unit)
Indicator
Indoor unit
Operation indicator
10 time flash
Timer indicator
8 time flash
Economy indicator
Continuous flash
Error code
E: A8
Detective actuator
Refrigerant leakage sensor
Forecast of cause
Refrigerant leakage
Check point 1. Refrigerant leakage detection conditions
•
When the refrigerant leakage sensor detects refrigerant.
•
System stop -> Cooling/heating cannot be operated.
•
Stir operation by fan -> Safety is important, and fan operation cannot be stopped.
-> Check for refrigerant leaks and take corrective action.
↓
Check point 2. Error release condition
Power on again.
•
If the power is not turned on again, the error will not be cleared even if the gas concentration
drops.
•
If the refrigerant leakage is detected again after the power is turned on again, an error will occur
again.
•
Replace the refrigerant leakage sensor as it will not recover if exposed to a high concentration
of gas or if exposed multiple times even if the concentration is not high.
↓
End
2-23. E: A8. Refrigerant leakage sensor error (Indoor unit)
- (03-28) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AGYG09KVCB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 10 05 SR_CH01_AG002EF_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 25 SR_CH02_AG002EF_02 ...
Page 37: ...3 TROUBLESHOOTING 2020 11 11 SR_CH03_AG002EF_01 ...
Page 39: ...5 1 Indoor unit 03 44 5 2 Outdoor unit 03 45 CONTENTS continued ...
Page 40: ......
Page 87: ...4 CONTROL AND FUNCTIONS 2020 11 11 SR_CH04_AG002EF_01 ...
Page 121: ...5 FILED WORKING 2020 11 11 SR_CH05_AG002EF_01 ...