8. Additional charge calculation
8-1. Model: AOU36RLXFZ1
Refrigerant type
R410A
Refrigerant amount
lb oz
7 lb 1 oz
g
3,200
¢
Refrigerant charge
•
3 or 4 indoor units are connected:
Total pipe length
ft
164 or less
197
230 (Max.)
0.22 oz/ft
(20 g/m)
m
50 or less
60
70 (Max.)
Additional charge
lb oz
0
7.1 oz
14.1 oz
g
0
200
400
•
2 indoor units are connected (with optional kit K9FZ1818):
Total pipe length
ft
65 or less
98
131 (Max.)
0.27 oz/ft
(25 g/m)
m
20 or less
30
40 (Max.)
Additional charge
lb oz
0
8.9 oz
1 lb 1.8 oz
g
0
250
500