7. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit
*
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H
H
7-1. Model: AOU24RLXFZ
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
¢
Indoor unit: 7,000 Btu
COOLING
Pipe length
m
5
7.5
10
15
20
25
m
ft
16
25
33
49
66
82
Height difference H
Indoor unit is higher than
outdoor unit *1
15
49
-
-
-
0.956
0.942
0.928
10
33
-
-
0.977
0.963
0.950
0.936
7.5
25
-
0.988
0.981
0.967
0.953
0.940
5
16
0.995
0.992
0.985
0.971
0.957
0.943
0
0
1.003
1.000
0.993
0.979
0.965
0.951
Indoor unit is lower than
outdoor unit *2
-5
-16
1.003
1.000
0.993
0.979
0.965
0.951
-7.5
-25
-
1.000
0.993
0.979
0.965
0.951
-10
-33
-
-
0.993
0.979
0.965
0.951
-15
-49
-
-
-
0.979
0.965
0.951
HEATING
Pipe length
m
5
7.5
10
15
20
25
m
ft
16
25
33
49
66
82
Height difference H
Indoor unit is higher than
outdoor unit *1
15
49
-
-
-
0.977
0.958
0.939
10
33
-
-
0.993
0.977
0.958
0.939
7.5
25
-
1.000
0.993
0.977
0.958
0.939
5
16
0.990
1.000
0.993
0.977
0.958
0.939
0
0
0.990
1.000
0.993
0.977
0.958
0.939
Indoor unit is lower than
outdoor unit *2
-5
-16
0.985
0.995
0.988
0.972
0.953
0.934
-7.5
-25
-
0.993
0.986
0.970
0.951
0.932
-10
-33
-
-
0.983
0.967
0.948
0.930
-15
-49
-
-
-
0.962
0.944
0.925
- 237 -
7-1. Model: AOU24RLXFZ
7. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOU24RLXFZ
OUTDOOR UNIT
AOU24RLXFZ