2-4. Floor type
Model name
AGU9RLF
AGU12RLF
AGU15RLF
Power supply
208/230 V ~ 60 Hz
Available voltage range
187—264 V
Capacity
Btu/h class
9,000
12,000
14,000
Input power
W
16
20
23
Running current
A
0.15
0.18
0.20
Fan
Airflow rate
Cooling
HIGH
CFM (m
3
/h)
312 (530)
353 (600)
383 (650)
MED
259 (440)
288 (490)
306 (520)
LOW
212 (360)
224 (380)
235 (400)
QUIET
159 (270)
159 (270)
159 (270)
Heating
HIGH
312 (530)
353 (600)
383 (650)
MED
270 (460)
300 (510)
318 (540)
LOW
224 (380)
241 (410)
253 (430)
QUIET
159 (270)
159 (270)
159 (270)
Type × Q'ty
Cross flow fan × 2
Motor output
W
16
Sound pressure level *
Cooling
HIGH
dB (A)
39
42
44
MED
34
36
38
LOW
28
30
31
QUIET
22
22
22
Heating
HIGH
39
42
44
MED
35
38
39
LOW
30
32
33
QUIET
22
22
22
Heat exchanger type
Dimensions (H × W × D)
in (mm)
14-7/8 × 21-5/8 × 1-1/16 (378 × 550 × 26.6)
Fin pitch
FPI
21
Rows × Stages
2 x 18
Pipe type
Copper tube
Fin type
Aluminium
Enclosure
Material
Polystyrene
Color
White
(Approximate color of Munsell N 9.25/)
Dimensions
(H × W × D)
Net
in (mm)
23-5/8 × 29-1/8 × 7-7/8 (600 × 740 × 200)
Gross
27-9/16 × 32-5/16 × 12-3/16 (700 × 820 × 310)
Weight
Net
lb (kg)
31 (14)
Gross
37 (17)
Connection pipe
Size
Liquid
in (mm)
Ø1/4 (Ø 6.35)
Gas
Ø3/8 (Ø 9.52)
Ø1/2 (Ø 12.70)
Method
Flare
Drain hose
Material
PVC
Size
in (mm)
Ø 9/16 (I.D.), Ø 11/16 (O.D.) [Ø 13.8 (I.D.), Ø 16.7 (O.D.)]
Operation range
Cooling
°F (°C)
64 to 90 (18 to 32)
%RH
80 or less
Heating
°F (°C)
60 to 86 (16 to 30)
Remote controller type
Wireless (Wired [option])
NOTES:
• The protective function might work when using it outside the operation range.
• *Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 12 -