Indoor unit: 24,000 Btu
COOLING
Pipe length
m
5
7.5
10
15
20
25
m
ft
16
25
33
49
66
82
Height difference H
Indoor unit is higher than
outdoor unit *1
15
49
-
-
-
0.978
0.969
0.953
10
33
-
-
0.986
0.986
0.977
0.961
7.5
25
-
0.988
0.990
0.990
0.981
0.965
5
16
0.989
0.992
0.994
0.994
0.984
0.968
0
0
0.997
1.000
1.002
1.002
0.992
0.976
Indoor unit is lower than
outdoor unit *2
-5
-16
0.997
1.000
1.002
1.002
0.992
0.976
-7.5
-25
-
1.000
1.002
1.002
0.992
0.976
-10
-33
-
-
1.002
1.002
0.992
0.976
-15
-49
-
-
-
1.002
0.992
0.976
HEATING
Pipe length
m
5
7.5
10
15
20
25
m
ft
16
25
33
49
66
82
Height difference H
Indoor unit is higher than
outdoor unit *1
15
49
-
-
-
0.964
0.939
0.913
10
33
-
-
0.988
0.964
0.939
0.913
7.5
25
-
1.000
0.988
0.964
0.939
0.913
5
16
1.008
1.000
0.988
0.964
0.939
0.913
0
0
1.008
1.000
0.988
0.964
0.939
0.913
Indoor unit is lower than
outdoor unit *2
-5
-16
1.003
0.995
0.983
0.959
0.934
0.909
-7.5
-25
-
0.993
0.981
0.957
0.932
0.907
-10
-33
-
-
0.978
0.954
0.929
0.904
-15
-49
-
-
-
0.949
0.925
0.899
- 302 -
7-1. Model: AOU36RLXFZ1
7. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOU36RLXFZ1
OUTDOOR UNIT
AOU36RLXFZ1