12) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the
outdoor unit is stopped during cooling operation.
Function number
Setting value
Setting description
Factory setting
49
00
Disable
♦
01
Enable
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the setting
on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.
13) Room temperature control for wired remote controller sensor
NOTE:
Before performing this setting, refer to Function 95.
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to "Both" (01).
Ensure that the thermo sensor icon is displayed on the remote controller screen.
Function number
Setting value
Setting description
Factory
setting
92
(For cooling)
93
(For heating)
00
No correction 0.0 °F (0.0 °C)
♦
01
No correction 0.0 °F (0.0 °C)
02
-1 °F (-0.5 °C)
More cooling
Less heating
03
-2 °F (-1.0 °C)
04
-3 °F (-1.5 °C)
05
-4 °F (-2.0 °C)
06
-5 °F (-2.5 °C)
07
-6 °F (-3.0 °C)
08
-7 °F (-3.5 °C)
09
-8 °F (-4.0 °C)
10
+1 °F (+0.5 °C)
Less cooling
More heating
11
+2 °F (+1.0 °C)
12
+3 °F (+1.5 °C)
13
+4 °F (+2.0 °C)
14
+5 °F (+2.5 °C)
15
+6 °F (+3.0 °C)
16
+7 °F (+3.5 °C)
17
+8 °F (+4.0 °C)
- 153 -
14-5. Function details
14. Function settings
MULTI TYPE
2, 3, 4 ROOMS TYPE
MULTI TYPE
2, 3, 4 ROOMS TYPE