- (04 - 67) -
O
U
TD
O
O
R U
N
IT
AO
G
30L
4
O
U
TD
O
O
R U
N
IT
AO
G
30L
4
INDOOR UNIT : 14000Btu (AO
G30L4)
H
H
Height difference H
1 Indoor unit is higher than outdoor unit.
2 Indoor unit is lower than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HEATING
Pipe length (m)
5
7.5
10
15
20
25
Height
difference H
(m)
1
Indoor unit is
higher than
outdoor unit.
15
-
-
-
0.972
0.945
0.919
10
-
-
0.992
0.972
0.945
0.919
7.5
-
1.000
0.992
0.972
0.945
0.919
5
1.000
1.000
0.992
0.972
0.945
0.919
0
1.000
1.000
0.992
0.972
0.945
0.919
2
Indoor unit
is lower than
outdoor unit
-5
0.995
0.995
0.987
0.967
0.940
0.914
-7.5
-
0.993
0.985
0.965
0.938
0.912
-10
-
-
0.982
0.962
0.935
0.910
-15
-
-
-
0.957
0.930
0.905
COOLING
Pipe length (m)
5
7.5
10
15
20
25
Height
difference H
(m)
1
Indoor unit is
higher than
outdoor unit.
15
-
-
-
0.955
0.937
0.922
10
-
-
0.974
0.962
0.945
0.930
7.5
-
0.988
0.978
0.966
0.948
0.934
5
0.992
0.992
0.982
0.970
0.952
0.937
0
1.000
1.000
0.990
0.978
0.960
0.945
2
Indoor unit
is lower than
outdoor unit
-5
1.000
1.000
0.990
0.978
0.960
0.945
-7.5
-
1.000
0.990
0.978
0.960
0.945
-10
-
-
0.990
0.978
0.960
0.945
-15
-
-
-
0.978
0.960
0.945
Summary of Contents for AB*G14LVTA
Page 62: ... 01 58 MULTI TYPE 2 3 4 ROOMS TYPE MULTI TYPE 2 3 4 ROOMS TYPE INSTALLATION PLACE ...
Page 64: ... 01 60 MULTI TYPE 2 3 4 ROOMS TYPE MULTI TYPE 2 3 4 ROOMS TYPE INSTALLATION PLACE Unit mm ...
Page 195: ...2 OUTDOOR UNIT 2 ROOMS TYPE MULTI TYPE AO G14LAC2 AO G18LAC2 DTR_AO082E_07 2014 05 30 ...
Page 202: ... 02 06 OUTDOOR UNIT AO G14 18L2 OUTDOOR UNIT AO G14 18L2 MODEL AO G18L2 ...
Page 203: ... 02 07 OUTDOOR UNIT AO G14 18L2 OUTDOOR UNIT AO G14 18L2 WIRING DIAGRAMS 444 MODEL AO G14L2 ...
Page 204: ... 02 08 OUTDOOR UNIT AO G14 18L2 OUTDOOR UNIT AO G14 18L2 MODEL AO G18L2 ...
Page 227: ... 02 31 OUTDOOR UNIT AO G14 18L2 OUTDOOR UNIT AO G14 18L2 SOUND LEVEL CHECK POINT 99999 ...
Page 231: ...3 OUTDOOR UNIT 3 ROOMS TYPE MULTI TYPE AO G18LAT3 AO G24LAT3 DTR_AO083E_07 2014 05 30 ...
Page 279: ... 03 47 OUTDOOR UNIT AO G18 24L3 OUTDOOR UNIT AO G18 24L3 SOUND LEVEL CHECK POINT 99999 ...
Page 283: ...4 OUTDOOR UNIT 4 ROOMS TYPE MULTI TYPE AO G30LAT4 DTR_AO078E_08 2014 05 30 ...
Page 289: ... 04 05 OUTDOOR UNIT AO G30L4 OUTDOOR UNIT AO G30L4 WIRING DIAGRAMS 444 MODEL AO G30L4 ...
Page 357: ... 04 73 OUTDOOR UNIT AO G30L4 OUTDOOR UNIT AO G30L4 SOUND LEVEL CHECK POINT 99999 ...