CAPACITY COMPENSATION RATE FOR PIPE LENGTH
6.
AND HEIGHT DEFFERENCE
INDOOR UNIT : 7000Btu (AO
G30L4)
H
H
Height difference H
1 Indoor unit is higher than outdoor unit.
2 Indoor unit is lower than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HEATING
Pipe length (m)
5
7.5
10
15
20
25
Height
difference H
(m)
1
Indoor unit is
higher than
outdoor unit.
15
-
-
-
0.976
0.957
0.938
10
-
-
0.991
0.976
0.957
0.938
7.5
-
1.000
0.991
0.976
0.957
0.938
5
1.000
1.000
0.991
0.976
0.957
0.938
0
1.000
1.000
0.991
0.976
0.957
0.938
2
Indoor unit
is lower than
outdoor unit
-5
0.995
0.995
0.986
0.971
0.952
0.933
-7.5
-
0.993
0.984
0.969
0.950
0.931
-10
-
-
0.981
0.966
0.947
0.929
-15
-
-
-
0.961
0.943
0.924
COOLING
Pipe length (m)
5
7.5
10
15
20
25
Height
difference H
(m)
1
Indoor unit is
higher than
outdoor unit.
15
-
-
-
0.955
0.941
0.927
10
-
-
0.976
0.962
0.949
0.935
7.5
-
0.988
0.980
0.966
0.952
0.939
5
0.992
0.992
0.984
0.970
0.956
0.942
0
1.000
1.000
0.992
0.978
0.964
0.950
2
Indoor unit
is lower than
outdoor unit
-5
1.000
1.000
0.992
0.978
0.964
0.950
-7.5
-
1.000
0.992
0.978
0.964
0.950
-10
-
-
0.992
0.978
0.964
0.950
-15
-
-
-
0.978
0.964
0.950
Summary of Contents for AB*G14LVTA
Page 62: ... 01 58 MULTI TYPE 2 3 4 ROOMS TYPE MULTI TYPE 2 3 4 ROOMS TYPE INSTALLATION PLACE ...
Page 64: ... 01 60 MULTI TYPE 2 3 4 ROOMS TYPE MULTI TYPE 2 3 4 ROOMS TYPE INSTALLATION PLACE Unit mm ...
Page 195: ...2 OUTDOOR UNIT 2 ROOMS TYPE MULTI TYPE AO G14LAC2 AO G18LAC2 DTR_AO082E_07 2014 05 30 ...
Page 202: ... 02 06 OUTDOOR UNIT AO G14 18L2 OUTDOOR UNIT AO G14 18L2 MODEL AO G18L2 ...
Page 203: ... 02 07 OUTDOOR UNIT AO G14 18L2 OUTDOOR UNIT AO G14 18L2 WIRING DIAGRAMS 444 MODEL AO G14L2 ...
Page 204: ... 02 08 OUTDOOR UNIT AO G14 18L2 OUTDOOR UNIT AO G14 18L2 MODEL AO G18L2 ...
Page 227: ... 02 31 OUTDOOR UNIT AO G14 18L2 OUTDOOR UNIT AO G14 18L2 SOUND LEVEL CHECK POINT 99999 ...
Page 231: ...3 OUTDOOR UNIT 3 ROOMS TYPE MULTI TYPE AO G18LAT3 AO G24LAT3 DTR_AO083E_07 2014 05 30 ...
Page 279: ... 03 47 OUTDOOR UNIT AO G18 24L3 OUTDOOR UNIT AO G18 24L3 SOUND LEVEL CHECK POINT 99999 ...
Page 283: ...4 OUTDOOR UNIT 4 ROOMS TYPE MULTI TYPE AO G30LAT4 DTR_AO078E_08 2014 05 30 ...
Page 289: ... 04 05 OUTDOOR UNIT AO G30L4 OUTDOOR UNIT AO G30L4 WIRING DIAGRAMS 444 MODEL AO G30L4 ...
Page 357: ... 04 73 OUTDOOR UNIT AO G30L4 OUTDOOR UNIT AO G30L4 SOUND LEVEL CHECK POINT 99999 ...