Installation Overview
Please Note for Residential and Commercial units;
1.
FujiClean Treatment systems are designed to accept straight
wastewater. However, some treatment train designs,
especially commercial systems, call for pretreatment, settling
and/or trash tanks.
2.
Fill tank with fresh water to LWL (Low Water Level) mark in
all three chambers once tank is set.
3.
See Installation Manual for uplift restraint detail.
4.
“Clearwater” water softener backwash should be discharged
directly to a separate drywell, leaching pool or other
approved area.
5.
Use licensed electrician for final wiring.
6.
Affix NSF labels in two locations, inside the inlet riser and on
the inside of the controller. (Does not apply to models CE21,
CE30 and CEN21)
7.
Installing contractor responsible for final landscaping,
seeding etc. Be certain that final grade pitches away from
treatment tank covers.
8.
Final inspection and startup shall be the responsibility of the
FujiClean USA certified O&M provider.
9.
Homeowner manual must be provided to, and reviewed with,
homeowner to assure proper use.
10.
Warranty Card (orange card supplied by FujiClean USA), must
be returned to FujiClean USA to activate warranty.
4” PVC inlet and outlet pipe
Pump Station
(not included) if
site conditions or
design dictates.
Systems will be typically delivered
with 6” risers affixed. Contractor
shall supply additional layers if
necessary to 24” maximum riser
height.
3/4” or 1” air line conduit connection to
tank. Refer to sizing table on page 16 of
this Manual. Air line should be less than
100’ and have 5 or fewer “elbows.” (If
site conditions will not allow, please
contact FujiClean for air pump upsize
calculation).
System vents through
house vent system.
For houses with house
traps installed, vent
system separately
through vent hole in
tank.
6
Bed tanks in 4”-6” sand or suitable (no rocks) native soil .
Fill set tank with fresh water to low water mark in all 3
chambers.
Backfill in tamped lifts with suitable native soil, sand,
peastone or equivalent that form fits to tank. No sharp rocks!
4-point lifting lugs. Use
for setting tank. Tank
must be level to within
1/8”. Do not use lifting
lugs for uplift restraint.
Float switch to alarm panel connection: Drill hole in riser. Use male
fitting and electrical conduit. Plug with sealant for water-tight seal.
Install on the recirculation line using provided hose clamp in the center
of 2
nd
chamber with 3-1/2” tether.
Hardwired
power
connection
Outdoor rated
outlet power
connection OR…
FujiClean recommends a protective housing with solid
base for air pump placement. Contractor to supply
material to locate and mount the alarm/control panel.
FujiClean
Treatment System
Site in accessible
location with proximity
to alarm panel. See
additional placement
notes in Installation
Manual.
Residential Models
CE5, CE7 and CE10
CEN5, CEN7 and CEN10
1/8” Air pressure line is not supplied
with panels that use current sensors.
Adapters and fittings, when
necessary, are supplied by Fuji
Clean USA for connection
between treatment system
and air pump.