2 - 46
Sharp PLC • 2
(JW-32CUH/33CUH)
Available PLC
Communication Setting
The recommended communication parameter setting of both PLC and POD is as follows:
PLC System Memory Setting (in case of a communication port)
Set communication condition in the system memory #234/235(for PG/COMM port 1) or #236/237(for PG/
COMM port 2) to communicate with a personal computer.
Available Memory
Port
1
19200bps
Even
Baud Rate
Parity
RS-422
Data Length
7
Transmission Control
Item
Setting of PLC
1
19200bps
Even
7
2
2
Stop Bit
Error Check
Comm. Parameter of POD
4-wire system (fixed)
Sumcheck (fixed)
Command mode (fixed)
PLC
JW-32CUH
JW-33CUH
RS-232C
PG/COMM2 [Wiring Diagram 1]
RS-422
PG/COMM1 [Wiring Diagram 2]
PG/COMM2 [Wiring Diagram 2]
Communication port
on a CPU unit
Select PLC Type
JW20
COM port
Link Unit
Wiring Diagram
16 Sharp PLC
•
2
16
Memory
TYPE
Remarks
X9XXX (register)
0
XXXXX (relay)
1
as word device
EXXXX (self-diagnosis)
2
bXXXX (timer counter)
3
Fn
(file register)
7
*
1