2 - 92
SIEMENS PLC • 1
(S5-90, S5-95U, S5-100U)
Available PLC
A similar program as RK512 is required.
*
1 When using [6ES5 734-1BD20] cable made by SIEMENS , connect cable of [ Wiring Diagram 2 ]
to the D-sub 25 pins side of [6ES5 734-1BD20] to communicate with POD .
Communication Setting
The recommended communication parameter setting of both PLC and POD is as follows:
Available Memory
The assigned memory is indicated while editing
the screen as illustrated:
Set the memory to the extent of the memory range of each PLC model.
Use TYPE number to assign indirect memory for macro programs.
32
<E.g.> DB003000
Block No.
Address No.
PLC
S5-90U
S5-95U
S5-100U
S5-95U
RS-232C [Wiring Diagram 1]
[6ES5 734-1BD20] cable made by SIEMENS
+ RS-232C [Wiring Diagram 2]
CP-521SI
(3964R Transmission Protocol)
Second serial interface
(3964R Transmission Protocol)
Select PLC Type
*
1
Link Unit
Wiring Diagram
S5
( S5 UG400 )
9600bps
Even parity
8
Baud Rate
Parity
Transmission
Code
Data Length
Stop Bit
1
Item
Setting of PLC
9600bps
Busy Signal
Hand Shake
Even
8
1
Comm. Parameter of POD
NO (fixed)
OFF (fixed)
Memory
TYPE
Remarks
DB
(data register)
0
Use memories more than DB3.
I
(input relay)
1
IW as word device
Read only
Q
(output relay)
2
QW as word device
Read only
F
(internal relay)
3
FW as word device
Read only
T
(timer/current value)
4
Read only
C
(counter/current value)
5
Read only
AS
(absolute address)
6
32 SIEMENS PLC
•
1
Summary of Contents for UG220H Series
Page 270: ...Appendix Ladder Transfer Function...