2 - 54
Matsushita PLC
Available PLC
Communication Setting
The recommended communication parameter setting of both PLC and POD is as follows:
*
If a tool port (the ladder port for RS-232C) of FP0 is used, the range of PLC parameter setting is
limited as below. Adjust PLC parameter setting to comm. parameter setting of POD.
Baud rate
: 9600, 19200bps
Parity
: Odd (fixed)
Data bit
: 8 (7 can be selected. Normally 8.)
Stop bit
: 1 (fixed)
Port
19200bps
Even
7 (ASCII)
Baud Rate
Parity
Transmission
Code
Data Bit
Stop Bit
1
Transmission Control
Control Signal
Item
Setting of PLC
19200bps
Even
7
1
Comm. Parameter of POD
"0" for 10, "1" for
1
1
Computer link system (fixed)
Invalid (fixed)
FP1
FP0
FP3
FP5
FP10
RS-232C port
on a CPU unit
RS-232C port
on a CPU unit
AFP3462
AFP3463
AFP5462
AFP5462
RS-232C tool port
on a CPU unit
RS-232C cable made by Matsushita
AFC8513
PLC
Link Unit
Wiring Diagram
RS-232C [Wiring Diagram 1]
RS-232C [Wiring Diagram 1]
RS-422 [Wiring Diagram 4]
RS-232C [Wiring Diagram 1]
RS-422 [Wiring Diagram 4]
RS-232C [Wiring Diagram 1]
RS-232C [Wiring Diagram 1]
RS-232C [Wiring Diagram 1]
RS-232C [Wiring Diagram 3]
FP10S
RS-232C port
on a CPU unit
RS-232C port
on a CPU unit
AFP3462
AFP3463
RS-232C [Wiring Diagram 1]
Select PLC Type
MEWNET
FP2
RS-232C tool port
on a CPU unit
RS-232C cable made by Matsushita
AFC8513
RS-232C [Wiring Diagram 2]
RS-232C port
on a CPU unit
19 Matsushita PLC
19
Summary of Contents for UG220H Series