General com-
ments regarding
multiple MPP
trackers
In the case of inverters with multiple MPP trackers, there are two independent PV inputs
(MPP trackers) available. These can be connected to a different number of modules.
When using for the first time, set up MPP TRACKER according to the respective config-
uration (also possible later in the menu area "Devices and system components" under
the menu item "Inverter").
Multiple MPP
tracker configura-
tion 6-10 KW
DC
( 25 A)
-
+
PV 1
Total current (I
dcmax
) less than or equal to 25 A
MPPT settings:
PV1:
ON
PV2:
OFF
DC
( 25 A)
-
-
+
+
+
-
PV 2
PV 1
Combined solar module strings with total current
(I
dcmax
) less than or equal to 25 A
MPPT settings:
PV1:
ON
PV2:
OFF
DC
(>25 A / 48,75 A)
-
-
+
+
-
PV 2
P
PV 1
+
-
+
+
-
Combined solar module strings with total current
(I
dcmax
) greater than 25 A
MPPT settings:
PV1:
ON
PV2:
ON
PV1 + PV2 (connected in parallel):
ON
IMPORTANT!
The maximum current load of a single ter-
minal is 25 A. PV connection strings with a
total current (I
dcmax
) of more than 25 A
must be split between both PV inputs
upstream of the terminals (≤ 48.75 A).
Splitting the current by bridging from PV 1
to PV 2 at the terminal is not permitted.
58
Summary of Contents for Symo GEN24 10.0
Page 2: ......
Page 10: ...10 ...
Page 11: ...General information 11 ...
Page 12: ...12 ...
Page 28: ...28 ...
Page 29: ...Backup power variant PV Point OP 29 ...
Page 30: ...30 ...
Page 32: ...32 ...
Page 33: ...Backup power variant Full Backup 33 ...
Page 34: ...34 ...
Page 41: ...Installation 41 ...
Page 42: ...42 ...
Page 82: ...82 ...
Page 83: ...Settings web interface of the inverter 83 ...
Page 84: ...84 ...
Page 104: ...104 ...
Page 105: ...Appendix 105 ...
Page 106: ...106 ...
Page 116: ...116 ...
Page 117: ...Circuit diagrams 117 ...