Cross section of
the DC cable
Cable diameter for the strain-relief device: max. 9 mm.
Cable diameter for the connection to the push-in terminal: max. 6 mm
IMPORTANT!
For double-insulated cables with a cable diameter over 6 mm, the external insulation
layer must be removed to connect to the push-in terminal.
Maximum altern-
ating current fuse
protection
NOTE!
National regulations, the grid operator's
specifications or other factors may
require a residual current circuit
breaker in the AC connection lead.
For this situation, a type A residual-current
circuit breaker is generally adequate. Nev-
ertheless, false alarms can be triggered for
the type A residual current circuit breaker
in individual cases and depending on local
conditions. For this reason, in accordance
with national legislation, Fronius recom-
mends that a residual current protection
device with a tripping current of at least
100mA suitable for frequency converters
be used.
NOTE!
The inverter can be used with max. an
automatic circuit breaker C 32 A.
53
EN
Summary of Contents for Symo GEN24 10.0
Page 2: ......
Page 10: ...10 ...
Page 11: ...General information 11 ...
Page 12: ...12 ...
Page 28: ...28 ...
Page 29: ...Backup power variant PV Point OP 29 ...
Page 30: ...30 ...
Page 32: ...32 ...
Page 33: ...Backup power variant Full Backup 33 ...
Page 34: ...34 ...
Page 41: ...Installation 41 ...
Page 42: ...42 ...
Page 82: ...82 ...
Page 83: ...Settings web interface of the inverter 83 ...
Page 84: ...84 ...
Page 104: ...104 ...
Page 105: ...Appendix 105 ...
Page 106: ...106 ...
Page 116: ...116 ...
Page 117: ...Circuit diagrams 117 ...