Technical data
Fronius Symo GEN24
6.0 / 6.0 Plus
8.0 / 8.0 Plus
10.0 / 10.0 Plus
DC input data
MPP voltage range
(at nominal output)
174 - 800 V
224 - 800 V
278 - 800 V
Max. input voltage
at 1000 W/m²/-10 °C in an open circuit
1000 V
Min. input voltage
80 V
Feed-in start voltage in grid operation
80 V
Max. input current (PV1 / PV2)
25.0 / 12.5 A
Max. short circuit current of solar modules (I
SC PV
)
37.5 / 18.75 A
Max. feedback current
4)
37.5 A
Number of inputs - PV1
2
Number of inputs - PV2
1
DC input data battery
Max. voltage
500 / 700 V *
* only with suitable protection against overvoltage in
the event of a fault, on the battery or between the
inverter and the battery.
Min. voltage
160 V
Max. current
22 A
Max. output
6000 W
8000 W
10,000 W
DC inputs
1
DC overvoltage category
(in accordance with IEC 62109-1)
2
AC input/output data
Nominal output power (P
nom
)
6000 W
8000 W
10,000 W
Max. output power
6000 W
8000 W
10,000 W
Nominal grid voltage
3 ~ EN 220V / 380V
3 ~ EN 230V / 400V
Min. grid voltage
154 V
1)
Max. grid voltage
280 V
1)
Max. output current
16.4 A
Nominal frequency
50 / 60 Hz
1)
Nominal frequency for Full Backup
53 / 63 Hz
1)
Total harmonic distortion
< 3 %
112
Summary of Contents for Symo GEN24 10.0
Page 2: ......
Page 10: ...10 ...
Page 11: ...General information 11 ...
Page 12: ...12 ...
Page 28: ...28 ...
Page 29: ...Backup power variant PV Point OP 29 ...
Page 30: ...30 ...
Page 32: ...32 ...
Page 33: ...Backup power variant Full Backup 33 ...
Page 34: ...34 ...
Page 41: ...Installation 41 ...
Page 42: ...42 ...
Page 82: ...82 ...
Page 83: ...Settings web interface of the inverter 83 ...
Page 84: ...84 ...
Page 104: ...104 ...
Page 105: ...Appendix 105 ...
Page 106: ...106 ...
Page 116: ...116 ...
Page 117: ...Circuit diagrams 117 ...