External temperature below which the heating circuit pump switches on in setback mode
7°C
If the external temperature falls below this value in setback mode, the heating circuit pumps and mixing valve
are activated.
Frost protection temperature
10°C
If the room temperature or the flow temperature is lower than the set value, the heating circuit pump will be
switched on and the heating circuit mixer keeps to the maximum heating circuit flow temperature that is set.
5.1.3 Heating - Times
System menu
Heating
⇨ See "Setting times" [page 13]
Menu overview and parameters
5
Heating
Operating Instructions RBG 3200 Touch | B0780115_en
19