2.1.2 Setting end jumpers
To ensure that the bus system continues to work properly,
the end jumpers (J) need to be set.
❒ If there is an RBG 3200 Touch at the end of a bus
system, the end jumper at this module must be set. All
the previous ones, with the exception of that at the
core module, have to be deleted.
2.1.3 Calibrate the display
Once the power supply has been switched on for the first time, the RBG 3200 Touch
starts by calibrating the display. To calibrate the touchscreen, you much press five
points indicated by a crosshair in the order shown.
NOTICE
Inaccurate calibration
If you do not tap the indicated points accurately, the control may stop working
properly and a software update may be required.
2.1.4 Setting the module address
Once the display has been calibrated, the module address must be set. If it is the first
RBG 3200 Touch in the bus system, set module address 1. Number any others in
sequence.
NOTICE! Do not select an address of 0 as it leads to malfunctions with the RBG 3200
Touch!